Electro-pneumatic Regulator ER100 

Instruction Manual 

 rev. 2.0

 

  

page 21 / 38

 

 

4.2. 

Function List

 

 

Display 

Name 

Displayed data (in run mode) 

Setting (in setting mode) 

 

Pressure 

display 

The pressure on the secondary side 
(outgoing pressure) is shown through the 
three-digit number LED display. 

Unit 

Bar

 

1digit = 0,01Bar 

 

Display F1 

 

Input signal 

selection 

Shows the selected input signal type.   

* When preset memory mode is 

selected (the 8 setting points), the 
currently selected preset number and 
target value are displayed. 

<In case of analog type> 

The analog input, preset memory 
input or direct memory input can be 
selected. 
In case of the preset or direct memory 
input, enter the setting in this mode. 

<In case of parallel type> 

The parallel input or direct memory 
input can be selected. 
In case of the direct memory input, 
enter the target value in this mode. 

Display F2 

 

Zero/span 

adjustment 

With “F2” it is possible to activate the 
Zero/Span adjustment mode. When 
activating this function, “F2.” is displayed, 
followed by the adjusted zero point setting 
(L) and the adjusted span point setting 
(H). 

 The factory setting is set to  the full 

scale which means that the display 
will be shown, i.e it is not activated. 

Use in the full scale or adjust the zero 
and span settings upon selection. 
If zero/span adjustment is selected, 
adjust the values in this mode to the 
desired values. 

Display F3 

 

Auto power-off 

With “F3” it is possible to activate the 
energy saving function. If activated, the 
LED display is automatically switched 
OFF after approx. 1 minute. The display is 
switched ON again simply by touching 
any of the keys. 

* The factory setting is set to 

de-activated and on the display  
will be shown. 

Select whether the auto power-off 
function activated or not.   

Note: The interval to auto power-off is 

about one minute. The interval 
may not be changed. 

 

Display F4 

 

Switch output 

Function 
“F4” 
available for 
regulator 
with switch 
output only. 

With “F4” it is possible to 
activate/de-activate the Switch Output 
function. When activating this function, 
the switching mode and limits have to be 
selected. There are two modes available.
If “mode 1” is selected, “F4.1” is 
displayed, followed by the “negative” limit 
setting point (L) and “positive” limit setting 
point (H) in one sequence. 
If “mode 2” is selected is selected, “F4.2” 
is displayed, followed by the lower limit 
setting point (L) and the upper limit setting 
point (H) in one sequence. 

 The factory setting is set to 

de-activated and on the display  
will be shown. 

 

Select whether the switch output 
function should be activated or not. 
If the function is activated, you can 
select either “mode 1” or “mode 2.” 
Enter the desired positive and negative 
limits (for mode 1) or the upper and 
lower limits (for mode 2). 

Note: The hysteresis cannot be 

adjusted. 

Display F5 

 

Proportional 

value change 

 

* only for 
model 
ER104-1

 

Proportional value change and the setting level 
can be checked. In case of “proportional value 
increase”, “F5.H” is displayed. In case of 
“proportional value decrease” , “F5.L” and the 
setting level are displayed alternately. 

* In the factory shipmentstate, the standard 
value (- -) is specified.

 

Operate in the standard value state, or 
operate with a desired proportional value 
upon selection. 

Only when “proportional value decrease” is 
selected, the desired proportional value level 
can be specified in this mode (in 10 steps).

 

 

 

Summary of Contents for ER100 Series

Page 1: ...pneumatic Regulator Series ER100 ANALOG INPUT TYPE ER104 x0 1 2xx PARALLEL INPUT TYPE ER104 xPxx Please read this instruction manual carefully before using this product particularly the section descr...

Page 2: ...many functions and mechanisms to ensure safety However improper operation could result in an accident To prevent such accidents please read this operation manual carefully for proper operation Please...

Page 3: ...23 4 3 5 Proportional Value Change Function F5 24 4 4 Setting Method 25 4 4 1 Input Signal Setting 25 4 4 1 1 Analog Type Input Signal Selection 25 4 4 1 2 Parallel Type Input Signal Selection 26 4 4...

Page 4: ...t cannot be carried out where the set pressure is not reached The residual pressure discharge valve discharges compressed air remaining inside the pneumatic circuit to prevent accidents caused by pneu...

Page 5: ...ics functionality and durability in a negative way For the pneumatic source use cleaned air from which the solids water and oil contents were eliminated sufficiently using an air dryer filter and oil...

Page 6: ...ay be affected by direct sunlight water or oil For operation in other than the specification requirements or for special purposes please contact Camozzi Drip proof environment The protective structure...

Page 7: ...piping work is started If the port seal is removed before piping work dirt may enter into the interior from the piping port thus causing trouble and malfunctions etc Sufficiently flush blow air pipes...

Page 8: ...Electro pneumatic Regulator ER100 Instruction Manual rev 2 0 page 8 38 Solid and liquid sealant Solid and liquid sealant Seal Tape Solid and liquid sealant...

Page 9: ...When supplying compressed air after connecting pipes check that high pressure is not supplied instantly Before supplying compressed air after connecting pipes check that that there are no air leaks at...

Page 10: ...ct or poor accuracy Stop the controllers and mechanical equipment and turn the power off before connecting wiring Sudden activation may cause unexpected actions possibly causing danger First while lea...

Page 11: ...u i t output pro tection circuit Signal generator max50mA Load 5 pin Power 11 pin analog input 1 pin preset bit1 2 pin preset bit2 3 pin preset bit3 10 pin common 13 pin monitor output 14 pin error o...

Page 12: ...1 pin preset bit1 2 pin preset bit2 3 pin preset bit3 10 pin common 13 pin monitor output 14 pin error output 15 pin Power max50mA output pro tection circuit Load Load Signal generator M a i n c i r...

Page 13: ...utput 15 pin Power max50mA 10 pin common Load Load output pro tection circuit 12 pin MSB bit10 11 pin bit9 9 pin bit8 8 pin bit7 7 pin bit6 6 pin bit5 4 pin bit4 3 pin bit3 2 pin bit2 1 pin LSB bit1 M...

Page 14: ...0mA 10 pin common Load Load output pro tection circuit 12 pin MSB bit10 11 pin bit9 9 pin bit8 8 pin bit7 7 pin bit6 6 pin bit5 4 pin bit4 3 pin bit3 2 pin bit2 1 pin LSB bit1 M a i n c i r c u i t 5...

Page 15: ...e top or side position while holding it securely in the hand Lock the D sub connector so that it does not come off To unlock hold the fixing base with a wrench or similar while unscrewing with a screw...

Page 16: ...ch output Error output Type of input 1 bit 2 bit 3 bit N A 24 VDC N A Common 0 10 VDC 0 5V DC 4 20 mADC N A Output 1 5VD C NPN or PNP output NPN or PNP output Power 0V PARALLEL input type ER D sub soc...

Page 17: ...e specified voltage for the source voltage and output If an excessive voltage is connected malfunction breakage of the sensor electric shock and or fire may be caused Also do not use loads exceeding t...

Page 18: ...Electro pneumatic Regulator ER100 Instruction Manual rev 2 0 page 18 38 3 2 Dimensions...

Page 19: ...Polyphenylen sulfite resin 7 Pilot chamber Polyphenylen sulfite resin 8 Body Aluminium alloy die casting 9 Pressure sensor 10 Diaphragm Special nitrile rubber 11 Relief seat Aluminium alloy 12 Steel b...

Page 20: ...upon detection of an excessive current If there is an upper or lower limit in the function setting one of the following is displayed or key Use the key to start various setting modes Use the key to se...

Page 21: ...in simply by touching any of the keys The factory setting is set to de activated and on the display will be shown Select whether the auto power off function activated or not Note The interval to auto...

Page 22: ...ssure Input signal type Analog input type ER104 x0xx ER104 x1xx ER104 x2xx Input signal type symbol Description Analog 0 10VDC input Analog 0 5VDC input Analog 4 20mADC input Preset memory input Selec...

Page 23: ...d 100 Control pressure 0 100 Input signal If adjustment is activated 100 Control pressure 0 100 Input signal Zero point L setting range 0 to 50 Span point H setting range 100 to 10 4 3 3 LED Auto Powe...

Page 24: ...d Only when proportional value decrease is selected the setting level can be selected among 10 steps Effect of proportional value increase According to some operation conditions such as piping and loa...

Page 25: ...The analog input specification may not be changed In case of analog input selection Factory setting After the data is settled the setting mode is canceled to return to screen F1 SET For two seconds or...

Page 26: ...et memory input press and hold the SET key at least for two seconds The preset memory input signal setting mode is canceled to return to screen F1 After the data is inserted the next number is After t...

Page 27: ...ove the cursor key Increase the value SET 2 sec or longer If the preset memory input or direct memory input is selected at F1 input signal selection function this function may not be used Only full sc...

Page 28: ...ter the data is inserted the setting mode is canceled to return to Enter the target value key Shift the cursor key Increase the value SET 2 sec or longer 2 sec or longer SET Enter the target value key...

Page 29: ...h increased proportional value After the data is settled the setting mode is canceled to return to screen F5 In case of operation with decreased proportional value After the data is settled the settin...

Page 30: ...s the keys against erroneous operation Unlock when changing settings Key locking method Press and hold at least for two seconds at the same time SET Key unlocking method Press and hold at least for tw...

Page 31: ...um input increment 1 Enter the negative allowable limit Range 00 to 50 Minimum input increment 1 F4 Switch output function In case of mode 1 Enter the positive allowable limit Range 00 to 50 Minimum i...

Page 32: ...etting Screen F1 Input signal setting Analog type Parallel type A0 A1 A2 Analog parallel input Screen F2 Zero span adjustment Full scale zero span adjustment non activated Screen F3 Auto power off Aut...

Page 33: ...is removed Check to see if the bowl and element fouling condition is normal 3 Control for compressed air leak in the piping connection part Check to see if the condition of the connection section espe...

Page 34: ...r agency An error is caused when memory is read or written Contact the nearest Camozzi sales office or agency The secondary pressure does not reach the setting continuously for five seconds Check the...

Page 35: ...e maximum flow rate Continuation of operation in this state causes substantial reduction of the life Examine the operation method Air beyond the relief performance flows into the secondary piping Cont...

Page 36: ...t at the minimum operating pressure The pressure does not descend The exhaust port path is blocked Examine the layout so that exhaust air is discharged from the R and EXH ports The source voltage is u...

Page 37: ...and Relay Direct memory set 0 05 to 5 Bar setting min width 0 01Bar setting resolution 0 01Bar 0 09 to 9 Bar setting min width 0 01Bar setting resolution 0 02Bar Hysteresis 3 3 0 5 F S or less Linear...

Page 38: ...ing min width 0 01Bar setting resolution 0 01Bar Hysteresis 3 3 0 5 F S or less Linearity 3 3 0 3 F S or less Resolution 3 3 0 2 F S or less Repeatability 3 3 0 3 F S or less Zero point fluctuation 0...

Page 39: ...iameter 04 Rc1 4 Control pressure 1 1 Bar 5 5 Bar 9 9 Bar Input signal 0 0 10VDC 1 0 5VDC 2 4 20mADC P Parallel 10bit Output signal AN 1 5V analog errorN NPN AP 1 5V analog errorP PNP SN switchN NPN e...

Page 40: ...40 38 6 4 Optional individual code G8X1 1 Cable 1m 3 Cable 3m G8X1 Cable for analog input type G8X2 Cable for parallel input type 1 G8X1 x 30 7 9 Fili 31 5 1000 G8X1 1 3000 G8X1 3 100 Shield line 6 G8...

Page 41: ...ual rev 2 0 page 41 38 ER 1 B1 B1 type bracket Floor installation type B2 B2 type bracket Wall installation type B1 ER1 B1 ER1 B2 4 full R 30 5 51 27 3 5 10 36 42 3 5 1 6 5 17 5 22 4 4 32 42 44 7 2 1...

Page 42: ...binary is 1001100110 Turn the input signal on at 1 and turn it off at 0 See the table below 7 2 Relationship between preset memory and input signal D sub socket pin No 12 11 9 8 7 6 4 3 2 1 Cable opt...

Reviews: