9.4
Filter Change
Filter Change without Service Bag - Standard Airflow Top
➔
Bottom
Precautions :
Make sure the airflow is shut off !
Wear adapted protective gear !
Step1 : Opening the Door
The door is held in position by 4
star-shaped knobs
Unscrew the knobs
and put them aside
Take the door off, avoid
scraping on the threaded rods
Step 2 : Extraction of the soiled filter
Please Note :
For a standard housing with airflow Top
➔
Bottom
the clamping system is located on the bottom of the filter,
the filter gasket is located on the top.
Particle Filters with a metal body may reach a weight
of 20-30 kg, depending of type and size.
Molecular filtration cells may weigh > 80 kg.
Anticipate the weight to be lifted !
Swing the locking lever 180°
to the right
to unlock filter
Pull the filter using the grip
Extract the filter by pulling gently
supporting the bottom
Take out the filter taking care
not to touch housing sides