Install & Operating Manual
CamSafe
Filter Change without Service Bag - Inverted Airflow Bottom
➔
Top
Precautions :
Make sure the airflow is shut off !
Wear adapted protective gear !
Step 1 : Opening the door
The door is held in position by 4
star-shaped knobs
Unscrew the knobs
and put them aside
Take the door off, avoid
scraping on the threaded rods
Step 2 : Extraction of the soiled filter
Please Note :
For an inverted housing with airflow Bottom
➔
Top
the clamping system is located on top of the filter,
and includes 1 spring-loaded locking plunger.
It blocks the clamping frame in its OPEN end position and keeps
the clamping system from being pulled out of the fully open
position by the weight of the filter.
Swing the locking lever 180°
to the left
to unlock filter
Start swinging the clamping lever to the left.
Pull on knob when feeling some resistance, and release again.
The plunger pin will engage the locking hole and lock the mechanism in its open end position.
PLEASE NOTE :
In this position, the UNLOCKED filter is hanging from the clamping frame.