The sensitivity
5
(=Sensitivity) of the loop detector can be adapted in 9 stages:
51 =
Lowest sensitivity,
59 =
Highest sensitivity,
54 =
Factory setting.
In a device with 2 outputs, output 2 can be either activated or deactivated.
Four different frequencies F1, F2, F3, F4* can be set in order to avoid interference when using several loop detectors.
The direction logic function can only be used with a 2-loop device. Direction logic must have been set in the basic function (see chapter 3.2). Detection
can be performed from:
➝
Loop 1 to loop 2
➝
From loop 2 to loop 1
➝
from both directions
Display after start-up:
1
Touch the «Mode» button once
to change to configuration
mode
Mode
Sim1
1
Display after start-up:
1
2
Touch the «Mode» button once
to change to configuration
mode
Mode
Sim1
1
Mode
Sim1
2
Loop 2 is
selected
Loop 1 is
selected
ASB (=
A
utomatic
S
ensitivity
B
oost). ASB is required in order to be able to recognise trailer drawbars after activation.
Basic function 2 «Barrier systems» or 3 «quiescent current» must be set for this function.
P 1
= Protection against power tailure activated: The sensitivity is restricted to 1–5 and the time function to h.
Time functions 1, time unit 2 and time factor 3 (see Table 4.1a for settings)
3.3
Sensitivity 4 (see Table 4.1a for settings)
3.4
Automatic Sensitivity Boost ASB
5
(see Table 4.1a for settings)
3.5
Frequency
6
(see Table 4.1a for settings)
3.6
Direction logic
7
(see Table 4.1a for settings)
3.7
Output 2
8
(see Table 4.1b for settings)
3.8
Protection against power failure
9
(see Table 4.1a for settings)
3.9
1- loop device
2- loop device
2
Signal characteristics with protection against power failure active (Function 9 = 1)
3.9.1
For Activation (e.g. Barriers)
4
Changeover from operation to configuration mode
The relay picks up when the
loop is activated and drops
out when the loop is exited.
Loop
Relay
On delay:
The relay picks up after the
time t when the loop is acti-
vated and drops out when
the loop is exited.
Loop
Relay
tt
Off delay:
The relay picks up when the
loop is activated and drops
out after the time t when the
loop is exited.
Loop
Relay
tt
Activation pulse:
The relay picks up when the
loop is activated and drops
out again after the time t.
Loop
Relay
tt
Impulse by leaving the loop:
By leaving the loop,
the relay picks up after
the time t, relay drops out.
Loop
Relay
tt
Max. presence:
he relay picks up when the
loop is activated and drops
out again after leaving, but
at least after the time t.
Loop
Relay
tt
Basic function 0 =
2 Barrier systems
Without power
Initialisation
Free
Occupied
Free
For Safeguarding (e.g. Barriers, bollards)
Basic function 0 =
3 Quiescent current
Without power
Initialisation
Free
Occupied
Free
common
nc
no
common
nc
no
common
nc
no
common
nc
no