Installation

The  SATK  series  HIU  is  designed  for  installation  in  a  sheltered

domestic environment (or similar), therefore cannot be installed or

used  outdoors,  i.e.  in  areas  directly  exposed  to  atmospheric

agents.  Outdoor  installation  may  cause  malfunctioning  and

hazards.

If  the  device  is  enclosed  inside  or  between  cabinets,  sufficient

space must be provided for routine maintenance procedures. It is

recommended that electrical devices are NOT placed underneath

the HIU, as they may be damaged in the event of safety relief valve

activation if not connected to a discharge tundish, or in the event of

leaks occurring at the hydraulic fittings. If this advice is not heeded,

the  manufacturer  cannot  be  held  responsible  for  any  resulting

damage.

In the event of a malfunction, fault or incorrect operation, the device

should  be  deactivated;  contact  a  qualified  technician  for

assistance.

Preparation

After  having  established  the  point  where  the  device  has  to  be

installed, perform the following operations: 

· Mark the holes required for securing the HIU to the wall

· Mark the position of the hydraulic connections

Check  the  measurements  again  and  begin  laying  the  following

lines:

• Hydraulic:

1. connection to the central system line

2. heating circuit connection

3. domestic water circuit connection

4.  conveyance  of  safety  relief  valve  and  charging  unit  backflow 

preventer discharge

• Electric:

1. 230 V (ac) – 50 Hz electric supply line

2. chrono-thermostat/thermostat line (potential-free)

3. centralised bus line for heat meter data transmission (if required)

4. centralised electric supply line for heat meter (if required)

Before installation, it is recommended to carry out accurate flushing

of  all  the  pipes  of  the  system  in  order  to  remove  any  residue  or

impurities that could endanger correct operation of the HIU. 
Fix the HIU to the wall

.

N.B.

the wall anchors (not supplied) can only guarantee effective

support  if  inserted  correctly  (in  accordance  with  good  technical

practice) into walls built using solid or semi-solid bricks. If working

with walls built using perforated bricks or blocks, mobile dividing

panels  or  any  masonry  walls  other  than  those  indicated,  a

preliminary static test must be carried out on the support system.

Electric connections

Make sure that the electrical system can withstand the maximum

power consumption of the appliance, with particular emphasis on

the cross-section of the cables.

If you have any doubts, contact a qualified technician to request a

thorough check of the electrical system.

Electrical  safety  of  the  appliance  is  only  achieved  when  it  is

correctly connected to an effective earthing system, constructed as

specified in current safety regulations. This is a compulsory safety

requirement. 

Heat meter installation

The HIU is designed to fit a compact heat meter (with incorporated

return probe) with 1” threaded connections and 130 mm gauge.

Before carrying out any maintenance, repair or part replacement

work, proceed as follows:

- cut off the electric supply

- remove the cover

- close the shut-off valves

- empty the HIU using the drain cocks provided

- remove the template (A)

- remove the cap (B)

- install the flow meter on the return pipe

- install the flow probe in the M10 pocket (B).

Please  refer  to  the  heat  meter  technical  data  sheets  for  further

information.

Connection to the main supply

The device is supplied with an electric supply cable which is not

fitted with a plug.

The device should be electrically connected to a 230 V (ac) single-

phase + earth mains supply using the three-wire cable marked with

the label as specified below, observing the LIVE (L) - NEUTRAL (N)

polarities and the earth connection. This line must be connected to

a circuit breaker device.

A

B

Summary of Contents for SATK30 Series

Page 1: ...9 10 11 12 13 Maintenance 14 Function The SATK series HIU allows independent control of heat regulation and domestic hot water production within centralised heating systems or served by district heati...

Page 2: ...at sources or high intensity electromagnetic fields This device cannot be used in areas at risk of explosion or fire 3 The device must be connected to an independent bipolar switch If work has to be d...

Page 3: ...s steel Technical specifications SATK30105HE Medium water Maximum percentage of glycol 30 Maximum medium temperature 85 C Max working pressure primary circuit 1 6 MPa 16 bar secondary circuit 0 3 MPa...

Page 4: ...impurities that could endanger correct operation of the HIU Fix the HIU to the wall N B the wall anchors not supplied can only guarantee effective support if inserted correctly in accordance with goo...

Page 5: ...ves as shown in the figure ON DHW CH FAULT 2 1 0 1 2 3 4 bar ON DHW CH FAULT 2 1 NOTES 1 Install water hammer arresters to compensate for any overpressure in the domestic water circuit 2 In the presen...

Page 6: ...SATK30 series HIU are fitted with a filling unit equipped with a backflow preventer C check valve D and cock A When filling the system for the first time or for subsequent top up procedures following...

Page 7: ...et point temperatures and error codes 88 Trimmers for set point settings They allow the setting of the temperature set point for the operating cycles and view the relative value on the display Dip swi...

Page 8: ...C and rising in regular intervals to a temperature of 45 C Once the maximum set point has been reached the function is executed following the same procedures in reverse from the maximum set point to t...

Page 9: ...y requests to run cycles not associated to the previous one will continue to run normally Heating probe fault Error code 5 5 Domestic water probe fault Error code 6 6 Compensation probe fault Error co...

Page 10: ...temperature setting 45 75 C Set point regulation DHW production range 42 60 C Optional functions Domestic cycle DHW pre heating function Heating cycle modulating temperature regulation with compensat...

Page 11: ...0105HE HIU is factory set to support low temperature heating 25 45 C according to the following switch setting To modify the factory settings and enable the HIU to support medium high temperature syst...

Page 12: ...rted Vessel pre charge check For correct operation of the system periodically check at least once every six months the vessel pre charge value Replacing the valve obturator Extract the fixing clip D a...

Page 13: ...R s EBRUIK DEZE ENKEL VOOR AANSLUITING OP CODE s 5TILICE SOLAMENTE PARA LA CONEXI N CON COD 7 8 Raumthermostat Potenzialfreier Kontakt Sonde d ambiance Contact sec Termostato de ambiente Contacto sin...

Page 14: ...call qualified personnel to have it serviced modulating valve actuator faulty call qualified personnel to have it replaced valve obturator blocked in intermediate position call qualified personnel to...

Page 15: ...mary circuit flow rate insufficient contact person in charge of system centralised system not working contact person in charge of system CH LED OFF chrono thermostat time setting incorrect check progr...

Page 16: ...ecifications and made in accordance with best practices 13 Are the shut off valves open 14 Has the visual inspection of the hydraulic connections given a positive result 15 Has the system primary been...

Reviews: