FAULT DESCRIPTION

INDICATIONS

POSSIBLE CAUSE OF FAULT

OPERATIONS TO BE PERFORMED

Water is not

heated

DHW LED ON

primary circuit shut-off valves closed

open the valves

modulating valve actuator connector disconnected

reconnect actuator connector

modulating valve actuator disconnected from valve body

reconnect actuator

modulating valve actuator faulty

call qualified personnel to have it

replaced

DHW temperature probe cable inverted with heating

probe

restore correct connection

presence of air in the system

vent the system

electronic controller not working

call qualified personnel to have it

replaced

valve obturator blocked in closed position

call qualified personnel to have it

replaced

centralised system not working/cold

contact person in charge of system

FAULT LED ON +

error code 6 active

DHW temperature probe disconnected

reconnect probe

DHW temperature probe faulty

call qualified personnel to have it

replaced

FAULT LED ON +

error code 79 active

incorrect switch setting

restore correct switch setting

FAULT LED ON +

error code 80 active

incorrect switch setting

restore correct switch setting

DHW LED OFF

DHW priority flow meter disconnected

reconnect flow meter

DHW priority flow meter faulty

call qualified personnel to have it

replaced

all LEDs are OFF

no electric power supply

restore HIU electric supply

protection fuse burnt out

call qualified personnel to have it

replaced

The water is hot

but does not

reach the

desired

temperature

DHW LED ON

domestic water cycle temperature set point too low

increase set point

primary circuit strainer of the HIU clogged

call qualified personnel to have it

serviced

heat exchanger partly clogged

call qualified personnel to have it

serviced

modulating valve actuator faulty

call qualified personnel to have it

replaced

valve obturator blocked in intermediate position

call qualified personnel to have it

replaced

modulating valve actuator connector disconnected

reconnect actuator connector

DHW temperature probe cable inverted with heating

probe

restore correct connection

excessive demand for DHW

decrease demand

electronic controller not working

call qualified personnel to have it

replaced

centralised system temperature insufficient

contact person in charge of system

primary circuit flow rate insufficient

contact person in charge of system

Hot water

temperature is

too high

DHW LED ON

domestic water cycle temperature set point too high

decrease set point

DHW temperature probe cable inverted with heating

probe

restore correct connection

modulating valve actuator faulty

call qualified personnel to have it

replaced

valve obturator blocked in intermediate or open position

call qualified personnel to have it

replaced

electronic controller not working

call qualified personnel to have it

replaced

primary circuit excessive pressure

contact person in charge of system

Hot water flow

rate is

insufficient

DHW LED ON

HIU strainer clogged

call qualified personnel to have it

serviced

possible domestic water system shut-off valves 

partially closed

open the valves

centralised domestic circuit cold water flow rate

insufficient

call qualified personnel to have it

serviced

Hot water flow

rate is zero

DHW LED OFF

possible domestic water system shut-off valves closed

open the valves

no cold water in centralised domestic circuit

call qualified personnel to have it

serviced

HIU strainer completely clogged

call qualified personnel to have it

serviced

heat exchanger completely blocked

call qualified personnel to have it

serviced

Troubleshooting

Summary of Contents for SATK30 Series

Page 1: ...9 10 11 12 13 Maintenance 14 Function The SATK series HIU allows independent control of heat regulation and domestic hot water production within centralised heating systems or served by district heati...

Page 2: ...at sources or high intensity electromagnetic fields This device cannot be used in areas at risk of explosion or fire 3 The device must be connected to an independent bipolar switch If work has to be d...

Page 3: ...s steel Technical specifications SATK30105HE Medium water Maximum percentage of glycol 30 Maximum medium temperature 85 C Max working pressure primary circuit 1 6 MPa 16 bar secondary circuit 0 3 MPa...

Page 4: ...impurities that could endanger correct operation of the HIU Fix the HIU to the wall N B the wall anchors not supplied can only guarantee effective support if inserted correctly in accordance with goo...

Page 5: ...ves as shown in the figure ON DHW CH FAULT 2 1 0 1 2 3 4 bar ON DHW CH FAULT 2 1 NOTES 1 Install water hammer arresters to compensate for any overpressure in the domestic water circuit 2 In the presen...

Page 6: ...SATK30 series HIU are fitted with a filling unit equipped with a backflow preventer C check valve D and cock A When filling the system for the first time or for subsequent top up procedures following...

Page 7: ...et point temperatures and error codes 88 Trimmers for set point settings They allow the setting of the temperature set point for the operating cycles and view the relative value on the display Dip swi...

Page 8: ...C and rising in regular intervals to a temperature of 45 C Once the maximum set point has been reached the function is executed following the same procedures in reverse from the maximum set point to t...

Page 9: ...y requests to run cycles not associated to the previous one will continue to run normally Heating probe fault Error code 5 5 Domestic water probe fault Error code 6 6 Compensation probe fault Error co...

Page 10: ...temperature setting 45 75 C Set point regulation DHW production range 42 60 C Optional functions Domestic cycle DHW pre heating function Heating cycle modulating temperature regulation with compensat...

Page 11: ...0105HE HIU is factory set to support low temperature heating 25 45 C according to the following switch setting To modify the factory settings and enable the HIU to support medium high temperature syst...

Page 12: ...rted Vessel pre charge check For correct operation of the system periodically check at least once every six months the vessel pre charge value Replacing the valve obturator Extract the fixing clip D a...

Page 13: ...R s EBRUIK DEZE ENKEL VOOR AANSLUITING OP CODE s 5TILICE SOLAMENTE PARA LA CONEXI N CON COD 7 8 Raumthermostat Potenzialfreier Kontakt Sonde d ambiance Contact sec Termostato de ambiente Contacto sin...

Page 14: ...call qualified personnel to have it serviced modulating valve actuator faulty call qualified personnel to have it replaced valve obturator blocked in intermediate position call qualified personnel to...

Page 15: ...mary circuit flow rate insufficient contact person in charge of system centralised system not working contact person in charge of system CH LED OFF chrono thermostat time setting incorrect check progr...

Page 16: ...ecifications and made in accordance with best practices 13 Are the shut off valves open 14 Has the visual inspection of the hydraulic connections given a positive result 15 Has the system primary been...

Reviews: