Operating cycles

Domestic cycle

This cycle always takes priority over the heating cycle.

When DHW cycle activation is requested, due to DHW tapping by

the user (detected by the domestic water flow meter), the regulator

modulates  the  valve  opening  in  order  to  adjust  the  temperature

detected  by  the  domestic  water  probe  to  the  selected  set  point

value.

When tapping ends, the modulating valve is fully closed.

The  active  domestic  hot  water  cycle  is  signalled  by  yellow  DHW

LED steady on.

The general domestic water cycle temperature set point can be set

using trimmer P1 and shown on the display.

Heating cycle 

Set point regulation

When heating cycle activation is requested by the room thermostat,

the  circulation  pump  is  powered  while  the  modulating  valve  is

opened gradually until the set point temperature is reached.

At the end of the heating cycle, the circulation pump comes to a

stop and the modulating valve is closed. The active heating cycle is

signalled by lighting of the yellow CH LED.

The heating cycle temperature set point can be set using trimmer P2

and shown on the display.

Floor slab heating function 

LOW temperature setting

Facilitates  the  installation  of  underfloor  heating  systems  at  low

temperatures. This function can only be activated and executed if

there are no faults.

It can be activated by pressing and holding the RESET button for 8

seconds.

The yellow CH LED blinks while the floor slab heating function is in

operation.

The  function  lasts  240  hours  and  is  carried  out  by  simulating  a

request to run in heating mode starting from a set point of 25°C and

rising  in  regular  intervals  to  a  temperature  of  45°C.  Once  the

maximum  set  point  has  been  reached,  the  function  is  executed,

following the same procedures, in reverse (from the maximum set

point to the minimum set point).

This function has priority over heating and hot water cycles, and

can be suspended at any time by pressing and holding the RESET

button for 8 seconds.

Optional  functions

(to  activate/deactivate  the  optional  functions

the electric power supply must always be turned off!)

Domestic cycle

DHW pre-heating function

The function is enabled by setting DIP switch 5 to the ON position.

During  periods  when  the  domestic  water  cycle  is  not  used,  if  the

DHW probe detects a temperature 10°C below the SET value, the

controller partially opens the domestic hot water modulating valve for

the  time  required  (max.  5  min.)  to  bring  the  exchanger  to  the

condition wherein it can assure rapid DHW production.

The  domestic  hot  water  pre-heating  function  is  signalled  by  the

flashing yellow DHW LED.

This function is less of a priority than any domestic water or heating

cycles.

Heating cycle

Modulating  temperature  regulation  with  compensated  set

point 

The function is enabled by setting DIP switch 1 to the OFF position.

When  the  function  is  enabled,  the  flow  temperature  is  modified

according to the temperature detected by the compensation probe

(located  on  the  user  return  pipe).  This  keeps  the  actual  thermal

output of the slab - and therefore the ambient thermal load - under

control. The thermal response time of the system is thus minimised.

If the function is enabled the display shows the return temperature,

and  the  flow  temperature  is  adjusted  in  accordance  with  the

following formula:

Flow temperature = Return tempe 

D

T

In 

MEDIUM/HIGH

temperature configuration: 

D

T = 8–22°C

At 

LOW

temperature setting: 

D

T = 2–8°C

Summary of Contents for SATK30 Series

Page 1: ...9 10 11 12 13 Maintenance 14 Function The SATK series HIU allows independent control of heat regulation and domestic hot water production within centralised heating systems or served by district heati...

Page 2: ...at sources or high intensity electromagnetic fields This device cannot be used in areas at risk of explosion or fire 3 The device must be connected to an independent bipolar switch If work has to be d...

Page 3: ...s steel Technical specifications SATK30105HE Medium water Maximum percentage of glycol 30 Maximum medium temperature 85 C Max working pressure primary circuit 1 6 MPa 16 bar secondary circuit 0 3 MPa...

Page 4: ...impurities that could endanger correct operation of the HIU Fix the HIU to the wall N B the wall anchors not supplied can only guarantee effective support if inserted correctly in accordance with goo...

Page 5: ...ves as shown in the figure ON DHW CH FAULT 2 1 0 1 2 3 4 bar ON DHW CH FAULT 2 1 NOTES 1 Install water hammer arresters to compensate for any overpressure in the domestic water circuit 2 In the presen...

Page 6: ...SATK30 series HIU are fitted with a filling unit equipped with a backflow preventer C check valve D and cock A When filling the system for the first time or for subsequent top up procedures following...

Page 7: ...et point temperatures and error codes 88 Trimmers for set point settings They allow the setting of the temperature set point for the operating cycles and view the relative value on the display Dip swi...

Page 8: ...C and rising in regular intervals to a temperature of 45 C Once the maximum set point has been reached the function is executed following the same procedures in reverse from the maximum set point to t...

Page 9: ...y requests to run cycles not associated to the previous one will continue to run normally Heating probe fault Error code 5 5 Domestic water probe fault Error code 6 6 Compensation probe fault Error co...

Page 10: ...temperature setting 45 75 C Set point regulation DHW production range 42 60 C Optional functions Domestic cycle DHW pre heating function Heating cycle modulating temperature regulation with compensat...

Page 11: ...0105HE HIU is factory set to support low temperature heating 25 45 C according to the following switch setting To modify the factory settings and enable the HIU to support medium high temperature syst...

Page 12: ...rted Vessel pre charge check For correct operation of the system periodically check at least once every six months the vessel pre charge value Replacing the valve obturator Extract the fixing clip D a...

Page 13: ...R s EBRUIK DEZE ENKEL VOOR AANSLUITING OP CODE s 5TILICE SOLAMENTE PARA LA CONEXI N CON COD 7 8 Raumthermostat Potenzialfreier Kontakt Sonde d ambiance Contact sec Termostato de ambiente Contacto sin...

Page 14: ...call qualified personnel to have it serviced modulating valve actuator faulty call qualified personnel to have it replaced valve obturator blocked in intermediate position call qualified personnel to...

Page 15: ...mary circuit flow rate insufficient contact person in charge of system centralised system not working contact person in charge of system CH LED OFF chrono thermostat time setting incorrect check progr...

Page 16: ...ecifications and made in accordance with best practices 13 Are the shut off valves open 14 Has the visual inspection of the hydraulic connections given a positive result 15 Has the system primary been...

Reviews: