Safety thermostat cut-out 

Error code 69

The  HIUs  configured  to  support  low  temperature  heating

continuously  monitor  the  safety  thermostat  controlling  the  flow

temperature.

If  the  safety  thermostat  is  activated  during  a  general  cycle,  the

heating  circulation  pump  immediately  comes  to  a  stop  and  the

modulating valve is completely closed. 

After  the  user  has  removed  the  block  imposed  by  the  safety

thermostat, operation can only be re-enabled when the modulating

valves are completely closed again.

This  means  that  if  a  domestic  water  cycle  is  in  progress,  the

activation of the shut-off valve will be postponed until the end of that

domestic water cycle.

Removing a fault

To  restore  the  operating  mode  press  the  manual

RESET button.

Safety and alarms

Error codes associated with faults signalled by illumination of the

FAULT LED are also shown on the display.

69

 

 

 

Removing a fault

Normal  operating  conditions  are  restored  automatically  once  the

faulty probe is working properly again (see page 12 - “Temperature

probe replacement”).

Probe fault

If a temperature probe fails, the associated cycle will be stopped

immediately and disabled.

Any requests to run cycles not associated to the previous one will

continue to run normally.

Heating probe fault 

Error code: 5

 

 5

 

Domestic water probe fault 

Error code: 6

 

 

 6

Compensation probe fault 

Error code: 15

 

 

 

Removing a fault

Restore  the  correct  switch  setting  in  accordance  with  the

procedure shown on pages 10-11.

Incorrect switch setting

Error code 79

79

 

 

 

Removing a fault

The heat interface unit is disabled due to incorrect setting of the

dip-switches. Restore the correct switch setting in accordance with

the procedure shown on pages 10-11.

Incorrect switch setting (heat interface unit disabled)

Error code 80

 

 

 

80

Heating circuit pressure switch fault 

Error code 4

The  electronic  regulator  continuously  monitors  the  status  of  the

pressure switch controlling the water pressure in the heating circuit.

If  the  pressure  switch  is  activated,  the  heating  circulation  pump

immediately comes to a stop and the modulating valve is completely

closed.

This fault implies the stoppage of the heating cycle only.

Domestic water drawing requests will continue to be served normally.

N.B.

: A low pre-charge value of the expansion vessel can cause a

pressure switch fault.

Removing a fault

Return to the operating mode is subordinate to restoration of the

correct water pressure in the secondary heating circuit (see page

6 - “Filling the user system”).

 4

 

 

Summary of Contents for SATK30 Series

Page 1: ...9 10 11 12 13 Maintenance 14 Function The SATK series HIU allows independent control of heat regulation and domestic hot water production within centralised heating systems or served by district heati...

Page 2: ...at sources or high intensity electromagnetic fields This device cannot be used in areas at risk of explosion or fire 3 The device must be connected to an independent bipolar switch If work has to be d...

Page 3: ...s steel Technical specifications SATK30105HE Medium water Maximum percentage of glycol 30 Maximum medium temperature 85 C Max working pressure primary circuit 1 6 MPa 16 bar secondary circuit 0 3 MPa...

Page 4: ...impurities that could endanger correct operation of the HIU Fix the HIU to the wall N B the wall anchors not supplied can only guarantee effective support if inserted correctly in accordance with goo...

Page 5: ...ves as shown in the figure ON DHW CH FAULT 2 1 0 1 2 3 4 bar ON DHW CH FAULT 2 1 NOTES 1 Install water hammer arresters to compensate for any overpressure in the domestic water circuit 2 In the presen...

Page 6: ...SATK30 series HIU are fitted with a filling unit equipped with a backflow preventer C check valve D and cock A When filling the system for the first time or for subsequent top up procedures following...

Page 7: ...et point temperatures and error codes 88 Trimmers for set point settings They allow the setting of the temperature set point for the operating cycles and view the relative value on the display Dip swi...

Page 8: ...C and rising in regular intervals to a temperature of 45 C Once the maximum set point has been reached the function is executed following the same procedures in reverse from the maximum set point to t...

Page 9: ...y requests to run cycles not associated to the previous one will continue to run normally Heating probe fault Error code 5 5 Domestic water probe fault Error code 6 6 Compensation probe fault Error co...

Page 10: ...temperature setting 45 75 C Set point regulation DHW production range 42 60 C Optional functions Domestic cycle DHW pre heating function Heating cycle modulating temperature regulation with compensat...

Page 11: ...0105HE HIU is factory set to support low temperature heating 25 45 C according to the following switch setting To modify the factory settings and enable the HIU to support medium high temperature syst...

Page 12: ...rted Vessel pre charge check For correct operation of the system periodically check at least once every six months the vessel pre charge value Replacing the valve obturator Extract the fixing clip D a...

Page 13: ...R s EBRUIK DEZE ENKEL VOOR AANSLUITING OP CODE s 5TILICE SOLAMENTE PARA LA CONEXI N CON COD 7 8 Raumthermostat Potenzialfreier Kontakt Sonde d ambiance Contact sec Termostato de ambiente Contacto sin...

Page 14: ...call qualified personnel to have it serviced modulating valve actuator faulty call qualified personnel to have it replaced valve obturator blocked in intermediate position call qualified personnel to...

Page 15: ...mary circuit flow rate insufficient contact person in charge of system centralised system not working contact person in charge of system CH LED OFF chrono thermostat time setting incorrect check progr...

Page 16: ...ecifications and made in accordance with best practices 13 Are the shut off valves open 14 Has the visual inspection of the hydraulic connections given a positive result 15 Has the system primary been...

Reviews: