• Compare the read values with those on the table.
• Change power every 10 minutes and wait for it to stabilise.
• Access the user menu and, if necessary, change the parameters.
Fig. 109 - Digital pressure switch connection (Atena
3
Plus12/14 - Duke 12/14 At - Saba 12/14)
DATA
P1
P2
P3
P4
P5
Stove depression -
temperature 12 kW 20 Pa - 105°C
32 Pa - 135°C
45 Pa - 165°C
63 Pa - 195°C
73 Pa - 215°C
Stove depression -
temperature 14 kW 20 Pa - 105°C
32 Pa - 140°C
40 Pa - 170°C
52 Pa - 205°C
63 Pa - 225°C
Fig. 110 - Digital pressure switch connection (Mithos
3
Plus12/14)
DATA
P1
P2
P3
P4
P5
Stove depression -
temperature 12 kW 17 Pa - 95°C
28 Pa - 130°C
37 Pa - 155°C
52 Pa - 180°C
58 Pa - 220°C
Stove depression -
temperature 14 kW 17 Pa - 95°C
26 Pa - 140°C
45 Pa - 175°C
55 Pa - 220°C
68 Pa - 240°C
NB: for good combustion, the depression values must be b -5 Pa and the temperature values b - 10°C.
6.22 CONNECTION TO THE EXTERNAL THERMOSTAT