CALCULATING RING LENGTH
Page C-4
Figure C-1. Wiring in a Single Wiring Closet
Formulas
Two formulas were used to create the tables for the STP Cable
Length Worksheets. The first defines the cabling for a single
wiring closet with only one rack and the second for multiple racks
within the wiring closet. The difference between the two
formulas accounts for cabling between racks within a wiring
closet. The term Internal Trunk Length refers to trunk cabling
length within the wiring closet, adjusted to give consideration to
ARL. The actual calculations used in the table are as follows:
30' of
Type 6
WALL
PLATE
WALL
PLATE
STATION 1
STATION 2
WIRING CLOSET
140' of
TYPE 1
LOBE CABLING
TRUNK CABLING
8 foot patch cables (Type 6)
used within racks
30'
30'
8'
8' of
Type 6
8'
185' of
TYPE 1
8'