Self-regulation of the functioning parameters (AUTO)

The first and most important function to program is the self-regulation of the parameters, which allows the control unit to auto-
matically set the end run points, the torque applied to the leaf and the slowing phases*.

During the autoset operations, the control unit automatically performs several opening and closure manoeuvres.
Before proceeding, check that no person, animal or obstacle is or can be in the door manoeuvre area.

Proceed as follows:
1- Apply mains power supply to the automation via the pre-wired socket, using an extension if necessary.
2- Release the leaves, take them manually to about half of the run and block them again.
3- Start the autoset phase as described below. As soon as the first manoeuvre starts, carefully check that:
a) both leaves must move in the closure direction. 
If this is not the case, press “5” and “PGM” at the same time to interrupt the autoset. The display shows the ERR message. 
Invert the M+/M- wires of the motor/s that moved in the opening direction.
b) the first motor to perform closure must be that connected to clamp M2. If this is not the case, invert the connections of mo-
tors M1 and M2.

1

Apply mains power supply by connecting the plug

2

Press the button [PGM] to access programming.

PGM

3

The display shows AUTO, select Auto by pressing the [PGM] button.

AUTO

4

AUTO starts to flash slowly. Press and hold the [PGM] key, after 5 seconds AUTO starts to flash 
quickly, release the key only when the display shows the PRG message.

5

The self-regulation phase starts, the display shows PRG. The control unit commands different open-
ing and closing manoeuvres at various speeds.

At the end of the manoeuvre the display shows “OK”

PRG

6

To go back to the programming menu, press the [PGM] and [

5

] buttons at the same time. 

To exit programming, remove the power supply or wait for 60 seconds. 

PGM+

5

* The slowing phase envisions that the last phase of manoeuvre, both opening and closure, are performed at a slower speed, 
thus allowing a silent manoeuvre.

The intervention of the photocells or any other command from the transmitter or key selector, interrupts the autoset 
phase, displaying the message ERR1/2/3.  The procedure must therefore be repeated.

Every self-regulation procedure overwrites the previous one.

Perform an autostop procedure after every maintenance intervention or modification of the door

.

Programming of the control unit allows the regulation of all 
parameters indispensable for the correct functioning of the 
automation.
Programming takes place by means of a series of menus that 
can be selected from the LCD. A function corresponds to every 
menu, which will be described successively. 

PGM

The “PGM” button allows to enter programming, 
select the pre-selected menu and confirm the 
value selected.

5

The “

5

” button allows to scroll the various items in 

the menu and the values to be set cyclically.

PGM+

5

By pressing “

5

” and “PGM” at the same time, 

return to the upper level of the menu or, if already 
at the first level, exit programming.

Programming the CP.JMP control unit - Introduction

LCD

PGM

With the display off, the “

5

” button performs a Step-

by-Step command. This function can be useful during 
the programming and inspection phases.

Summary of Contents for BEAUTY

Page 1: ...L8543185 ENG 03 2016 rev 0 Complete kit for the automation of swinging gates Instructions and Recommendations for installation and use MADE IN ITALY BEAUTY...

Page 2: ...Sld 20 Resetting the control unit Res 20 Memorising new transmitters RADI PP 21 Memorising pedestrian function RADI Ped 21 Deleting transmitters RADI CLR 22 Complete deletion of the receiver memory R...

Page 3: ...ve received instructions for use by people in charge of their security Check that the temperature range marked on the drive is suitable for the location The drive cannot be used with a driven part inc...

Page 4: ...or wall installation 1 transmitter TX 1 receiver RX 8 BTY 3 Release keys for manual manoeuvre 9 Plugs and screws for fixing the accessories flashing light key selector photocells 10 F BY Flashing ligh...

Page 5: ...epend on the state of the gate structure Check that there is enough space for installation of the operator in safe and comfortable conditions Technical Data dimensions and limits of use TECHNICAL DATA...

Page 6: ...ce with the wiring rules 2 It is recommended not to exceed 15 m in length If it is indispensable to exceed this limit increase the section of the cable 3 As the receiver photocell labelled RX requires...

Page 7: ...too different to each other do not allow regular movement of the leaves and could cause malfunctioning Detect the value of the measurement M precisely and state it in every box in column M in Table 1...

Page 8: ...ues for positioning of the brackets BTY 1 Adjustable brackets BTY 1 Using the adjustable brackets BTY 1 it is possible to install the BEAUTY gear reducer with different installation measurements witho...

Page 9: ...de the gear motor BTY 1 It is important to consider the correspondence between the height established and the presence of gate support structures Fig 9 Fig 10 Fig 11 C F V D R Fig 12 2 The electrical...

Page 10: ...is perfectly horizontal and then mark the two points for drilling the leaf fig 17 V R2 R1 Also in this case the fixing devices will be selected on the basis of the material with which the leaf is mad...

Page 11: ...ated in the Electric connec tions paragraph Fig 21 P A Fixing the CP BTY control unit With reference to the Electric connections chapter Fig 5 select the most suitable position for fixing the control...

Page 12: ...screws are supplied for fixing the flashing light Make two holes with diameter of 6 mm Insert the cable and fix the base using the plugs and screws ANT SHIELD Connections ANT SHIELD Connect the 24V fl...

Page 13: ...ge of the cables Four 6 mm plugs and relative screws are supplied for fixing the photocells Make two holes with diam eter of 6 mm in a way that the hole in proximity of the terminal board corresponds...

Page 14: ...selector Two 6 mm plugs and relative screws are supplied for fixing the selector base to the wall V Using the support as a reference mark and make two holes with diameter of 6 mm in a way that the lo...

Page 15: ...ansmitter for the long distance commands for BYOU automations Functioning The transmitter has three buttons through which it is possible to command the various functions of the automation configurable...

Page 16: ...ED 24 Vdc flashing light connection output MOT1 ORANGE Motor 1 connection output respect red and blue ref C MOT2 ORANGE Motor 2 connection output respect red and blue ref C SHIELD ANT BLUE Connection...

Page 17: ...essage 5 The self regulation phase starts the display shows PRG The control unit commands different open ing and closing manoeuvres at various speeds At the end of the manoeuvre the display shows OK P...

Page 18: ...re time TCA The automatic closure function allows to set a time which on expiry if the leaf is in the open position the control unit autono mously commands a closure manoeuvre With this function activ...

Page 19: ...on of commands is performed cyclically OPEN STOP CLOSE STOP OPEN and so on The sequence can be modified by eliminating the intermediate STOP commands OPEN CLOSE OPEN and so on 1 Press the PGM button t...

Page 20: ...lation The display shows the current value of the Sld parameter Use the 5 key to select one of these values ON reduced speeds OFF standard speed default on off 3 Confirm the desired value using the PG...

Page 21: ...ramming menu press the PGM and 5 buttons at the same time Press the PGM and 5 buttons twice at the same time to go back to the main Radi menu To exit programming remove the power supply or wait for 60...

Page 22: ...PP Press 5 three times to display the RTR sub menu rtr 3 Press the PGM button to enter the RTR function Press and hold PGM the RTR message starts to flash quickly 4 When the RTR message switches off r...

Page 23: ...ry power supply cable with a mains con nection that is in compliance with the Standards in force and the type of installation COMMISSIONING Commissioning of the automation can only be performed if all...

Page 24: ...re present release the motor and check for the presence of friction points Perform a new self learning Increase the value of the PMOT parameter The door does not close STOP input active Obstacle betwe...

Page 25: ...st be followed regarding differentiated disposal and re cycling of the various components metals plastics electric cables etc It is advised to contact a BYOU specialised technician or a specialised co...

Page 26: ...2006 42 CE OF EH EUROPEAN PARLIAMENT AND COUNCIL 17 May 2006 in relation to ma chinery amending Directive 95 16 CE in relation to the requisites for partly completed machinerys per the following harm...

Page 27: ......

Page 28: ...BYOU un marchio di Automatismi Beninc SpA via Capitello 45 36066 Sandrigo VI ITALY Tel 39 0444 1510294 Fax 39 0444 759728 info byouweb com www byouweb com...

Reviews: