6 2 1 Establishing a sewage system
connection
13
14
OUT
IN
►Connect the overflow hose Ø 24 mm (
13
) to the
product.
►Route the overflow hose with an incline of at
least 10 cm to the sewage system connection
(drain), or connect it to the included siphon in
accordance with the installation instructions and
fasten it sufficiently.
►Connect the rinsing water hose Ø 8 mm (
14
) to
the product.
►
Route the rinsing water hose to the sewage
system connection (drain) or connect it to the
included siphon.
►
Check the plug connection by pulling the connec-
tor back slightly.
NOTE
►
In accordance with EN 1717, the rinsing
water and overflow hoses must be connect
-
ed to the sewage system at least 20 mm
above the highest possible waste water level
(unimpeded drainage).
►
The flushing water and overflow hoses
must not be connected or constricted at
any point.
►Place the floor sensor on the floor.
> 20 mm
16
15
19
18
17
1 2 3
6 3
Electrical connections
The following connections are available at the rear
of the Easy Fill technology cover:
15 LAN (RJ45) connection
16 GSM antenna connection (optional, at low
signal strength)
17 Dosing pump connection (2-wire)
18 Fault signal contact connection (3 wire),
potential-free changeover contact (max.
24 V / 0.5 A) Terminal assignment:
Terminal 1-2 closed during operation
Terminal 3-2 closed during fault
19
Network cable (country-specific)
Connect the product to the power supply only