OIL BURNERS
Table VIII: Carlin Burner Specifications
Boiler
Model
Burner
Input
(GPH)
Burner
Mfr.
Burner
Model
Air Tube
Comb.
Burner Settings
Pump Pressure
(PSI)
Nozzle
Make
Nozzle Data
Head
Air
Band
Air Damper
Low High
Low
Fire
High
Fire
V903A
3.1
Carlin
301CRD 8” - Style ‘B’
1/4”
60%
N/A
N/A
---
150
Delavan
2.50 x 80° - B
V904A
4.2
Carlin
301CRD 8” - Style ‘B’
1/2”
100%
N/A
N/A
---
150
Hago
3.50 x 80° - SS
V905A
5.6
Carlin
301CRD 8” - Style ‘C’
34”
100%
N/A
N/A
---
150
Hago
4.50 x 80° - SS
V906A
7.0
Carlin
702CRD
10” Std.
7/32”
N/A
1/2”
Open
100
300
Hago
4.00 x 60° - P
V907A
8.3
Carlin
702CRD
10” Std.
1/2”
N/A
1/2”
Open
100
300
Hago
5.00 x 60° - P
V908A
9.6
Carlin
702CRD
10” Std.
3/4”
N/A
1/2”
Open
100
300
Hago
5.50 x 60° - P
V909A
11.6
Carlin
801CRD
10” Std.
1/4”
N/A
1/4”
Open
150
150
Hago
(L) 5.50 x 45° - H
(H) 4.00 x 45° - H
V910A
13.2
Carlin
801CRD
10” Std.
9/16”
N/A
1/4”
Open
150
150
Hago
(L) 6.50 x 45° - H
(H) 4.50 x 45° - H
V911A
14.8
Carlin
801CRD
10” Std.
3/4”
N/A
1/2”
Open
150
150
Hago
(L) 6.00 x 45° - H
(H) 6.00 x 45° - H
V912A
16.4
Carlin
801CRD
10” Std.
3/4”
N/A
1/2”
Open
150
150
Hago
(L) 7.00 x 45° - H
(H) 6.50 x 45° - H
SECTION VII - REPAIR PARTS
All V9A Series Repair Parts may be obtained through your local Burnham Wholesale distributor. Should
you require assistance in locating a Burnham Distributor in your area, or have questions regarding the
availability of Burnham products or repair parts, please contact Burnham Customer Service at 888-791-3790
or Fax (717) 293-5803.
Summary of Contents for operating and
Page 2: ...2 ...
Page 8: ...8 Section I General Information Figure 1 Dimensional Information ...
Page 21: ...21 Figure 16 Bare Boiler Assembly ...
Page 25: ...25 Figure 22 V9A Series Jacket Assembly Boiler Models V903A thru V912A ...
Page 31: ...31 Figure 26 V9A Series Minimum Piping Parallel Water Boiler ...
Page 32: ...32 Figure 27 V9A Series Minimum Piping Primary Secondary Water Boiler ...
Page 33: ...33 Figure 28 V9A Series Minimum Piping Details Bypass with Blend Pump Water Boiler ...
Page 34: ...34 Figure 29 V9A Series Minimum Piping Primary Secondary with Bypass Water Boiler ...
Page 37: ...37 Figure 32 Minimum Piping Requirements For Gravity Return V9A Series Steam Boilers ...
Page 42: ...42 Figure 37b DHW Generation with Tankless Coils Storage Tank and Destratification Pump ...
Page 43: ...43 Figure 37c DHW Generation with Indirect Water Heater ...
Page 58: ...58 Figure 40 Bare Boiler Assembly ...
Page 62: ...62 SERVICE RECORD DATE SERVICE PERFORMED ...
Page 63: ...63 SERVICE RECORD DATE SERVICE PERFORMED ...
Page 64: ...64 ...