53
Boiler
Model
Burner
Input
(GPH)
Burner Mfr.
Burner
Model
Diffuser
Blade
Setting
Damper Settings
Top / Bottom Damper
Pump Pressure (PSI)
Nozzle
Make
Nozzle Data
Low Fire
High Fire
Low Fire High Fire
GPH x
Angle-Type
V904A
4.2
Power Flame
C1-OS
1/8
1/4” / Closed
3/4” / 1/4”
100
270
Delavan
2.50 x 90° - B
V905A
5.6
Power Flame
C1-OS
1/4
Closed / 1/2”
3/8” / 7/8”
100
295
Delavan
3.25 x 80° - B
V906A
7.0
Power Flame
C1-OS
1/4
3/8” / 3/16”
7/8” / 9/16”
100
300
Delavan
4.00 x 80° - B
V907A
8.3
Power Flame
C1-OS
1/2
1/2” / Closed 11/16” / 3/16”
100
275
Delavan
5.00 x 70° - B
V908A
9.6
Power Flame
C2-OAS
1/8
1/2” / Closed
1/2” / 1”
100
260
Delavan
6.00 x 80° - B
V909A
11.6
Power Flame
C2-OAS
1/4
3/8” / 1/16”
3/4” / 5/16”
100
275
Delavan
7.00 x 80° - B
V910A
13.2
Power Flame
C2-OAS
1/4
3/8” / 1/4”
7/8” / 1/2”
100
275
Delavan
8.00 x 80° - B
V911A
14.8
Power Flame
C2-OB
1/4
1/2” / 1/4”
1-1/8” / 5/8”
100
270
Delavan
9.00 x 80° - B
V912A
16.4
Power Flame
C2-OB
1/4
3/4” / 1/4”
1-1/4” / 3/4”
100
270
Delavan 10.00 x 80° - B
Table VI: Power Flame Burner Specifications
OIL BURNERS
GAS BURNERS
Boiler
Model
Burner
Input
(MBH)
Burner Mfr.
Burner
Model
Diffuser No.
(or Diffuser
Blade Setting
Damper Settings
Top / Bottom Damper
Manifold Pressure
“W.C.
** Minimum Inlet
Pressure “W.C.
Low Fire
High Fire
Nat. Gas LP Gas
(1)
Nat.
Gas
LP Gas
(1)
V903A
447
Power Flame JR15A-10
J20611
1/8” / 1/8”
3/8” / 3/8”
3.5
3.5
4.0
4.0
V904A
606
Power Flame JR30A-10
J20610
1/8” / 1/8”
5/8” / 5/8”
3.4
3.4
4.2
4.2
V905A
808
Power Flame JR30A-12
J20615
1/16” / 1/16”
7/16” / 7/16”
3.4
3.4
4.1
4.1
V906A
1010
Power Flame JR30A-12
J20615
1/16” / 1/8”
13/16” / 7/8”
2.1
2.1
4.3
4.3
V907A
1198
Power Flame JR50A-15
J20607
1/4” / 1/4”
1” / 1”
2.3
2.3
5.4
5.4
V908A
1386
Power Flame JR50A-15
J20607
Closed / Closed 1-1/4” / 1-1/4”
2.7
2.7
4.4
4.4
V909A
1674
Power Flame JR50a-15
J20599
5/16” / 1/8”
3/4” / 7/8”
2.4
2.4
5.0
5.0
V910A
1905
Power Flame C2-G-20A
1/4”
3/8” / 1/4”
7/8” / 1/2”
1.8
1.8
5.2
5.2
V911A
2136
Power Flame C2-G-20B
1/4”
1/2” / 1/4”
1-1/8” / 5/8”
2.0
2.0
5.4
5.4
V912A
2367
Power Flame C2-G-20B
1/4”
3/4” / 1/4”
1-1/4” / 3/4”
3.4
3.4
5.0
5.0
* COMBINATION GAS / OIL BURNERS
Boiler
Model
Burner Input
Burner Mfr.
Burner
Model
Diffuser
Blade
Setting
Damper Settings
Top / Bottom Damper
Manifold
Pressure “W.C.
** Minimum Inlet
Pressure - “W.C.
Oil
(GPH)
Gas
(MBH)
Low Fire
High Fire
Low
Fire
High
Fire
Nat.
Gas
LP Gas
(1)
V904A
4.2
606
Power Flame
C1-GO-10
1/8
1/4” / Closed
3/4” / 1/4”
3.6
3.6
4.4
4.4
V905A
5.6
808
Power Flame
C1-GO-10
1/4
Closed / 1/2”
3/8” / 7/8”
3.0
3.0
4.4
4.4
V906A
7.0
1010
Power Flame
C1-GO-12
1/4
3/8” / 3/16”
7/8” / 9/16”
2.6
2.6
4.8
4.8
V907A
8.3
1198
Power Flame
C1-GO-12
1/2
1/2” / Closed 11/16” / 3/16”
2.1
2.1
5.2
5.2
V908A
9.6
1386
Power Flame
C2-GO-15
1/8
1/2” / Closed
1/2” / 1”
2.1
2.1
6.4
6.4
V909A
11.6
1674
Power Flame C2-GO-20A
1/4
3/8” / 1/16”
3/4” / 5/16”
2.3
2.3
4.9
4.9
V910A
13.2
1905
Power Flame C2-GO-20A
1/4
3/8” / 1/4”
7/8” / 1/2”
1.8
1.8
5.2
5.2
V911A
14.8
2136
Power Flame C2-GO-20B
1/4
1/2” / 1/4”
1-1/8” / 5/8”
2.0
2.0
5.4
5.4
V912A
16.4
2367
Power Flame C2-GO-20B
1/4
3/4” / 1/4”
1-1/4” / 3/4”
3.4
3.4
5.0
5.0
*
SEE OIL BURNER DATA ABOVE FOR NOZZLE SIZES AND PUMP PRESSURE SETTINGS.
**
MINIMUM INLET PRESSURE FOR UL GAS TRAINS ONLY. CONSULT FACTORY FOR ADDITIONAL INFORMATION.
NOTES:
(1) Burner not approved in Canada for LP gas.
Summary of Contents for operating and
Page 2: ...2 ...
Page 8: ...8 Section I General Information Figure 1 Dimensional Information ...
Page 21: ...21 Figure 16 Bare Boiler Assembly ...
Page 25: ...25 Figure 22 V9A Series Jacket Assembly Boiler Models V903A thru V912A ...
Page 31: ...31 Figure 26 V9A Series Minimum Piping Parallel Water Boiler ...
Page 32: ...32 Figure 27 V9A Series Minimum Piping Primary Secondary Water Boiler ...
Page 33: ...33 Figure 28 V9A Series Minimum Piping Details Bypass with Blend Pump Water Boiler ...
Page 34: ...34 Figure 29 V9A Series Minimum Piping Primary Secondary with Bypass Water Boiler ...
Page 37: ...37 Figure 32 Minimum Piping Requirements For Gravity Return V9A Series Steam Boilers ...
Page 42: ...42 Figure 37b DHW Generation with Tankless Coils Storage Tank and Destratification Pump ...
Page 43: ...43 Figure 37c DHW Generation with Indirect Water Heater ...
Page 58: ...58 Figure 40 Bare Boiler Assembly ...
Page 62: ...62 SERVICE RECORD DATE SERVICE PERFORMED ...
Page 63: ...63 SERVICE RECORD DATE SERVICE PERFORMED ...
Page 64: ...64 ...