6
Figure 2: Section Tappings
Table 1: Trim and Control Installation in Section Tappings
Tapping Size
(NPT)
Steam Boiler with
Probe L.W.C.O.
Steam Boiler with
Float L.W.C.O.
Water Boiler
Water Boiler with
Tankless Heater
A
2
Supply
Supply
Supply
Supply
B
½
Bush to ¼
Pressure Gauge
Plug
Plug
Plug
C
½
Gauge Glass
Nipple & ½ Union
Gauge, L.W.C.O. Street
Elbow, Syphon & Limit
Plug Lower Tapping Bush
to ¼ Upper Tapping
Press./Temp. Gauge
Plug Lower Tapping Bush to
¼ Upper Tapping
Press./Temp. Gauge
D
2
Return
Return
Bush to 1½, 3" Npl, Elbow,
2" Npl, Circ. Flange,
Gasket, Circulator Return
Bush to 1½, 3" Npl, Elbow,
2" Npl, Circ. Flange,
Gasket, Circulator Return
E
¾
3" Nipple & Street Elbow
Safety Relief Valve
3" Nipple & Street Elbow
Safety Relief Valve
3" Nipple & Street Elbow
Safety Relief Valve
3" Nipple & Street Elbow
Safety Relief Valve
F
2
Bush to ¾ Drain Valve
and/or Optional Return
Bush to ¾ Drain Valve
and/or Optional Return
Bush to ¾ Drain Valve and/or
Optional Gravity Return
Bush to ¾ Drain Valve and/or
Optional Gravity Return
G
2
Optional Supply (IN3-6)
Required Supply (IN7-12
Optional Supply (IN3-6)
Required Supply (IN7-12
Plug (IN3-12)
Optional Gravity Supply
Plug (IN3-12)
Optional Gravity Supply
H
¾
Bush to ¼ &
Syphon Limit
Bush to ¼
Pressure Gauge
Well
Limit
Well
Limit
J
¾
Not Applicable
Not Applicable
Not Applicable
Tankless Heater
K
¾
Low Water Cutoff
Plug
Plug
Plug
L
1
Factory Plugged
Surface Blow-Off
Factory Plugged
Surface Blow-Off
Factory Plugged
Factory Plugged
M
1¼
Factory Plugged
Alliance Return
Factory Plugged
Alliance Return
Factory Plugged
Factory Plugged
N
1¼
Factory Plugged
Alliance Supply
Factory Plugged
Alliance Supply
Factory Plugged
Factory Plugged
P
¾
Factory Plugged
Alliance Limit
Factory Plugged
Alliance Limit
Factory Plugged
Factory Plugged
Summary of Contents for INDEPENDENCE IN10 CANADA
Page 4: ... Figure 1 Dimensional Drawing ...
Page 18: ...18 Figure 25 Recommended Water Piping for Circulator Zoned Heating System ...
Page 19: ...19 Figure 25A Recommended Water Piping for Zone Valve Zoned Heating System ...
Page 28: ...28 Figure 34 Vent Damper Schematic Wiring Diagram Figure 33 Vent Damper Harness to Limit ...
Page 29: ...29 THIS PAGE LEFT INTENTIONALLY BLANK ...
Page 30: ...30 Figure 35 Wiring Diagrams Steam Continuous Ignition Standing Pilot Probe Low Water Cutoff ...
Page 32: ...32 Figure 36 Wiring Diagrams Steam Intermittent Ignition EI Probe Low Water Cutoff ...
Page 34: ...34 Figure 37 Wiring Diagrams Steam Continuous Ignition Standing Pilot Float Low Water Cutoff ...
Page 36: ...36 Figure 38 Wiring Diagrams Steam Intermittent Ignition EI Float Low Water Cutoff ...
Page 40: ...40 Figure 40 Wiring Diagrams Water Intermittent Ignition EI Intermittent Circulation ...
Page 42: ...42 Figure 41 Wiring Diagrams Water Continuous Ignition Standing Pilot Gravity Circulation ...
Page 44: ...44 Figure 42 Wiring Diagrams Water Intermittent Ignition EI Gravity Circulation ...
Page 46: ...46 Figure 43 Wiring Diagrams Water Continuous Ignition Standing Pilot Tankless Heater ...
Page 48: ...48 Figure 44 Wiring Diagrams Water Intermittent Ignition EI Tankless Heater ...
Page 51: ...51 Figure 48 Lighting Instructions Continuous Ignition System VR8200 and VR8300 Gas Valves ...
Page 52: ...52 Figure 49 Lighting Instructions Continuous Ignition System 7000 ERHC Gas Valve ...
Page 66: ...66 Honeywell Electronic Ignition Trouble Shooting Guide ...
Page 67: ...67 Honeywell Hot Surface to Pilot Trouble Shooting Guide ...
Page 80: ...80 ...
Page 84: ...84 ...
Page 87: ...87 THIS PAGE LEFT BLANK INTENTIONALLY ...
Page 88: ...88 ...