K.
Steam Boiler with Intermittent Ignition (EI) and Float
Low Water Cutoff. See Figure 38.
1. Normal Operation
a. Thermostat calls for heat. Thermostat Isolation
Relay is energized, closing contacts.
b. Vent Damper (if used) opens as stated in Vent
Damper Sequence of Operation.
c
.
Ignition Module is energized. Pilot Valve opens
and Igniter is energized to ignite Pilot Burner.
d. Sensor proves presence of pilot flame. Main
Valve(s) opens and ignites Main Burners.
e
.
After Thermostat is satisfied Ignition Module is
de-energized, extinguishing pilot and main
flame. Vent Damper (if used) closes.
2. Safety Shutdown
a
.
Limit: Automatically interrupts main burner
operation when steam pressure exceeds set point.
Maximum allowable pressure is 15 psi. Normal
operation resumes when system pressure falls
below set point.
b
.
Low Water Cutoff (LWCO): Automatically
interrupts main burner operation when surface of
boiler water falls to lowest permissible operating
level. Normal operation resumes when water
returns to normal level.
c
.
Blocked Vent Switch. Automatically interrupts
main burner operation when excessive vent
system blockage occurs. Control is a multiple
use device. If blocked vent switch is activated do
not attempt to place boiler in operation. Correct
source of blockage and reset blocked vent
switch.
d
.
Flame Roll-out Switch. Automatically interrupts
boiler operation when flames or excessive heat
are present in vestibule. Control is single use
device. If flame roll-out switch is activated do
not attempt to place boiler in operation. Correct
source of blockage and replace flame roll-out
switch.
e
.
Igniter/Sensor: senses pilot flame and causes
ignition module to turn off main burner and pilot
burner gas flow should pilot burner flame
extinguish. Five to six minutes after shutdown,
Ignition Module restarts ignition sequence.
For Electronic Ignition Trouble Shooting Guide,
see Page 65. For LED Status Codes, see Tables
8 and 9 on pages 55 and 56.
Summary of Contents for INDEPENDENCE IN10 CANADA
Page 4: ... Figure 1 Dimensional Drawing ...
Page 18: ...18 Figure 25 Recommended Water Piping for Circulator Zoned Heating System ...
Page 19: ...19 Figure 25A Recommended Water Piping for Zone Valve Zoned Heating System ...
Page 28: ...28 Figure 34 Vent Damper Schematic Wiring Diagram Figure 33 Vent Damper Harness to Limit ...
Page 29: ...29 THIS PAGE LEFT INTENTIONALLY BLANK ...
Page 30: ...30 Figure 35 Wiring Diagrams Steam Continuous Ignition Standing Pilot Probe Low Water Cutoff ...
Page 32: ...32 Figure 36 Wiring Diagrams Steam Intermittent Ignition EI Probe Low Water Cutoff ...
Page 34: ...34 Figure 37 Wiring Diagrams Steam Continuous Ignition Standing Pilot Float Low Water Cutoff ...
Page 36: ...36 Figure 38 Wiring Diagrams Steam Intermittent Ignition EI Float Low Water Cutoff ...
Page 40: ...40 Figure 40 Wiring Diagrams Water Intermittent Ignition EI Intermittent Circulation ...
Page 42: ...42 Figure 41 Wiring Diagrams Water Continuous Ignition Standing Pilot Gravity Circulation ...
Page 44: ...44 Figure 42 Wiring Diagrams Water Intermittent Ignition EI Gravity Circulation ...
Page 46: ...46 Figure 43 Wiring Diagrams Water Continuous Ignition Standing Pilot Tankless Heater ...
Page 48: ...48 Figure 44 Wiring Diagrams Water Intermittent Ignition EI Tankless Heater ...
Page 51: ...51 Figure 48 Lighting Instructions Continuous Ignition System VR8200 and VR8300 Gas Valves ...
Page 52: ...52 Figure 49 Lighting Instructions Continuous Ignition System 7000 ERHC Gas Valve ...
Page 66: ...66 Honeywell Electronic Ignition Trouble Shooting Guide ...
Page 67: ...67 Honeywell Hot Surface to Pilot Trouble Shooting Guide ...
Page 80: ...80 ...
Page 84: ...84 ...
Page 87: ...87 THIS PAGE LEFT BLANK INTENTIONALLY ...
Page 88: ...88 ...