12
I. Product Description, Specifications and Dimensional Data (continued)
Table 2C: Rating Data - Models aLP150 thru aLP285 (001 to 10,000 Feet Elevation above Sea Level)
alpine Series gas-Fired Boilers
Model
Number
*
Input
(MBH)
** Output
(MBH)
Net I=B=R
Ratings
Water (MBH)
AFUE
%
Thermal
Efficiency
(%)
Combustion
Efficiency (%)
Boiler Water
Volume
(Gal.)
Heat Transfer
Area (Sq. Ft.)
Min.
Max.
ALP150
38
113
104
90
95
1.3
16.4
ALP210
53
158
145
126
95
1.7
21.8
ALP285
68
204
188
163
95
2.4
29.1
* Add Suffix “F” for Floor mounted Models or Suffix “W” for Wall mounted Models.
notes:
** DOE Heating Capacity (ALP150 thru ALP285)
Maximum Working Pressure, Water - 30 PSI Shipped from Factory (std.); 50 PSI - Optional
Maximum Allowable Temperature, Water - 210°F
Boilers are factory shipped as Natural Gas builds
only
.
Input has been de rated for noted elevation above sea level.