102
Xii. Operation (continued)
E.
Adjusting Parameters
From the “Home” screen select the Adjust button to access the adjustment mode screens show below (if required, refer to the
previous page to review how to enter Adjustment mode):
The following pages describe
Sage2.1’s adjustable parameters.
Parameters are presented in the order
they appear on the Sage2.1 Display,
from top to bottom and, left to right
Pump
Setup
- More -
Manual
Control
Contractor
Setup
System
Setup
Modulation
Setup
Outdoor
Reset
Remote
4-20mA
Central
Heat
DHW
Sequencer
Master
Sequencer
Slave
“Press”
System
Setup
button to access the following parameters:
Factory
Setting
Range /
Choices
Parameter and Description
Fahrenheit
Fahrenheit,
Celsius
Temperature Units
The Temperature Units parameter determines whether temperature is represented in units of Fahrenheit or
Celsius degrees.
30%
0-100%
Display Brightness
Display brightness is adjustable from 0 to 100%.
30%
0-100%
Display Contrast
Display contrast is adjustable from 0 to 100%.
Installed
Not Installed,
Installed
Outdoor Sensor Source
Not Installed Outdoor Sensor is not connected to the boiler, the sensor is not monitored for faults.
Installed Outdoor Sensor is installed and monitored for faults.
note:
Enabling Frost Protection, Warm weather shutdown or Outdoor Air Reset functions will automatically
install the outdoor sensor. If you choose to disable these features and not use the outdoor sensor, press the “Not
Installed” selection to remove the outdoor sensor from fault monitoring screens.
Disabled
Enable/Disable
Frost Protection
Disable Frost Protection is not used.
Enable Boiler and system circulators start and boiler fires when low outside air, supply and return
temperatures are sensed as follows:
Disabled
Enable/Disable
Warm weather shutdown enable
Disable Warm Weather Shutdown (WWSD) is not used.
Enable
The boiler will not be allowed to start in response to a central heat call for heat if the outside
temperature is greater than the WWSD setpoint. The boiler will still start in response to a
Domestic Hot Water call for heat.
70°F
0-100°F
Warm weather shutdown setpoint
The Warm Weather Shutdown (WWSD) Setpoint used to shutdown the boiler when enabled by the “WWSD En
-
able” parameter.
Device
Start
Temperatures
Stop
Temperatures
Boiler & System
Pump
Outside Air < 0°F
Supply Water < 45°F
Outside Air > 4°F
Supply Water > 50°F
Boiler
Supply Water < 38°F
Supply Water > 50°F
Summary of Contents for Alpine ALP080
Page 40: ...40 Figure 29 Condensate Trap and Drain Line V Condensate Disposal continued ...
Page 56: ...56 VIII Electrical continued ...
Page 57: ...57 VIII Electrical continued Figure 35 Wiring Connections Diagram ...
Page 58: ...58 Figure 36 Ladder Diagram VIII Electrical continued ...
Page 64: ...64 Figure 39 Modular Boiler Direct Vent Termination X Modular Installation continued ...
Page 65: ...65 Figure 40 Modular Boiler Concentric Vent Termination X Modular Installation continued ...