Pneumatic installation
8
PNEUMATIC INSTALLATION
8.1
Safety instructions
DANGER
Risk of injury from high pressure and discharge of medium.
▶
Before working on the device or system, switch off the pressure. Vent or drain lines.
WARNING
Risk of injury from improper installation.
▶
Only trained technicians may perform installations.
▶
Perform installations with suitable tools only.
WARNING
Risk of injury due to unintentional activation and uncontrolled start-up of the system.
▶
Secure system against unintentional activation.
▶
Ensure that the system does not start up in an uncontrolled manner.
8.2
Connecting the device pneumatically
Exhaust air port, label: 3
Pilot air port, label: 1
Figure 23:
Connecting the device pneumatically
Important information for the problem-free functioning of the device:
▶
The installation must not cause back pressure to build up.
▶
Select a hose with sufficient cross section for the connection.
▶
Design the exhaust air line in such a way that no water or other liquid can get into the device
through the exhaust air port.
▶
The pressure supply must always be at least 0.5–1 bar above the pressure required to bring the
actuator into its end position.
→
Connect the control medium to the pilot air port (1)
(3–7 bar, instrument air, oil-free, anhydrous and dust-free).
→
Connect the exhaust air line or a silencer to the exhaust air port (3).
Exhaust air system:
▶
To maintain the IP67 degree of protection, install an exhaust air line in the dry area.