18
Technical data
6.6.1
Safety end positions
Safety end positions after failure of the electrical or pneumatic auxiliary power:
Actuator system
Designation
Safety end positions after failure of the auxiliary
power
electrical
pneumatic
up
down
single-acting
control function A
down
down
up
down
single-acting
control function B
up
up
up
down
double-acting
control function I
down
not defined
Table 1:
Safety end positions
6.7
Communication
6.7.1
IO-Link
Port Class
A
B
IO-Link specification
V1.1.2
Supply
via IO-Link (M12 x 1, 5-pin, A-coded)
SIO-Mode
No
IODD-File
see internet
VendorID
0x0078, 120
DeviceID
see IODD file
ProductID
8691 Class A
8691 Class B
Transmission speed
COM3 (230,4 kbit/s)
PD Input Bits
48
PD Output Bits
8
M-sequence Cap.
0x0D
Min. cycle time
5 ms
Data storage
Yes
Max. cable length
20 m
english
Type 8691 REV.3