2
About the appliance
Logano plus SB325 – 6 720 806 328 (2013/07)
9
2.12.2 Unit data
Boiler flow
1)
.
Ø VK
DN
R 1 ½
H
VK
mm
1178
Drain/boiler return 1
1)
Ø RK1
DN
R 1 ½
H
RK1
mm
156
106
Boiler return 2
1)
Ø RK2
DN
R 1 ¼
H
RK2
mm
506
Safety valve/Flow
safety line
2)
Ø VSL
DN
R 1
H
VSL
mm
1069
Minimum pressure switch
connection
3)
MDW
DN
G ¼
Condensate outlet
External diameter
mm
32
H
AKO
mm
257.5
207.5
1) According to DIN 2633 PN
2) According to EN 1092-1 PN 16.
3) As a replacement for low water level limiter
Boiler size
Abbreviations
Unit
50
70
90
115
Rated heat input for gas
[burner output Qn (H
i
)]
Full load, max.
kW
47.4
66.4
85.3
109.0
Partial load 40 %
kW
19.0
26.6
34.1
43.6
Net weight
kg
294
300
314
321
Water content
l
237
233
250
240
Gas content
l
90
120
138
142
Available draught
Pa
50
1)
/subject to burner
1) Maximum recommended pressure difference
Pressure drop on the hot gas side
mbar
0.43
0.50
0.59
0.77
Pressure drop on the water side
mbar
Fig. 4 , page 10
Standby loss
%
Fig. 5, page 10
Maximum flow temperature
2)
2) Safety limit (high limit safety cut-out). Maximum possible flow temperature = safety limit (high limit safety cut-out setting) - 18 K.
Example: Safety limit (high limit safety cut-out) = 100 °C, max. possible flow temperature = 100 - 18 = 82 °C.
°C
110
Maximum operating pressure
bar
4
Boiler with CE designation
CE-0085 AT 0074
Tab. 6 Unit data
Boiler size
50
70
90
115
Tab. 5 Unit data