9
Installing the control panel
Logano G615 - Subject to technical modifications
41
9.2
Installing set of temperature
sensors
B
Route the capillaries through the cable duct and unroll
to the required length.
B
Guide the capillaries to the corresponding sensor wells
and secure with the clips (magnified view in Fig. 53 is
rotated by 180°).
B
Attach cable entry (
Æ
Fig. 52) to the left and right of
the boiler rear panel.
Fig. 53 Fastening the connecting cables
1
Sensor wells
2
Sensor retaining clip
3
Cable entry
4
Cable strain relief
Both sensor wells have already been installed in the
supply (
Æ
Chapter 7.5, page 24).
The sensors (control panel sensor TRK, manual reset high
limit and Logamatic sensor FK or thermostat sensor) are
installed in the sensor wells.
The sensors must be arranged as follows:
B
Push the control panel sensor TRK out of the sensor
spacer by pressing it lightly.
Fig. 54 Temperature sensor set
B
Insert the control panel sensor in the sensor well R ½ "
and secure with a screw.
B
Insert the manual reset high limit (STB) and Logamatic
FK plus the two sensor spacers in the sensor well
R ¾ " and secure with a clip.
Fig. 55 Installing set of temperature sensors
NOTICE:
Appliance damage from damaged
capillaries.
B
Make sure that the capillaries are not
crushed or otherwise compromised
during unrolling and routing.
The manual reset high limit (STB) can be
distinguished from the control panel sensor.
6 720 642 625-47.1o
FK
STB
TRK
6 720 642 625-48.1o
FK
STB
TRK
R3/4"
R1/2"