6
Positioning the boiler
Logano G615 - Subject to technical modifications
17
6.3
Installing the boiler on a boiler base
or foundation
Fig. 6
Base dimensions
Place the boiler on a 2 – 4 inch (450 – 100 mm) tall base
(observe wall clearances). The base must be flat and level.
The front edge of the boiler should be flush with the edge
of the base.
When pouring a foundation for the boiler, use the steel
inserts with the following dimensions:
3 15/16 × 1 31/32 × 5/16 inches (100 × 50 × 8 mm)
or sheet metal with the dimensions
3 15/16 × 13/64 inches (100 × 5 mm).
A silencing boiler base is available as an
accessory from Buderus.
6 720 642 621-01.1o
L
2
(820 mm)
(~ 100 mm)
(100 mm)
(~ 1160 mm)
(~ 50...100 mm)
2...4"
L
1
34 3/4"
1
4"
4"
32 9/32"
(410 mm)
16 9/64"
(100 mm)
4"
16 9/64"
34 3/4"
32 9/32"
Number of
boiler sections
L1 (base)
inch (mm)
L2 (steel section)
inch (mm)
9
65 3/4“ (1670)
57 7/8“ (1470)
10
72 7/16“ (1840)
64 9/16“ (1640)
11
79 9/64“ (2010)
71 1/4“ (1810)
12
85 53/6“4 (2180)
77 61/64“ (1980)
13
92 33/64“ (2350)
84 41/64“ (2150)
14
99 7/32“ (2520)
91 11/32“ (2320)
15
105 29/32“ (2690)
98 1/32“ (2490)
16
112 19/32“ (2860)
104 23/32“ (2660)
Tab. 9
Base dimensions for angle or sheet metal steel
lengths