90
We reserve the right to make any changes due to technical modifications!
Installation and Servicing Instructions Logamax plus GB142-24/30/45/60 • Version 12/2004
Buderus Hydronic Systems • http://www.buderus.net
Appendix
16
z
The gas orifice diameter is marked on the gas
orifice (in mm).
z
The venturi article number is marked on both clips of
the venturi (see fig. 140, pos. 1 and 2).
Type of gas
supply
Factory pre-setting of the gas control valve
Natural gas
Delivered factory-set: Natural Gas
LPG
P
Suitable for propane after conversion (also
see the chapter "Conversion to another
type of gas supply").
Information on gas type instruction plate:
Set to gas category: Propane.
Table 17 Factory setting of the gas control valve
Fig. 140 Venturi article number
1
2
Thermal
power gas
appliance
Type of gas
supply
Gas orifice
diameter in
mm (inch)
Type of
orifice
above
4,500 ft
Venturi
article
number
GB142-24
Natural gas
4.45 (0.174)
4.65 (0.181)
423.072A
LPG
P
3.35 (0.131)
3.35 (0.131)
423.072A
GB142-30
Natural gas
4.45 (0.174)
4.65 (0.181)
423.072A
LPG
P
3.35 (0.131)
3.35 (0.131)
423.072A
GB142-45
Natural gas
5.35 (0.209)
5.55 (0.216)
423.072A
LPG
P
4.05 (0.158)
4.05 (0.158)
423.072A
GB142-60
Natural gas
7.25 (0.283)
7.45 (0.291)
423.072A
LPG
P
5.35 (0.209)
4.05 (0.158)
423.072A
Table 18 Gas orifice diameter