Servicing
14
77
We reserve the right to make any changes due to technical modifications!
Installation and Servicing Instructions Logamax plus GB142-24/30/45/60 • Version 12/2004
Buderus Hydronic Systems • http://www.buderus.net
14.27 Condensate trap; replacing
z
Disconnect the heating system from the power
supply, remove the main fuse or switch off the circuit
breaker.
z
Set the main switch on the BC10 to "0" (Off).
z
Remove the casing.
z
Pull the condensate trap from the condensate plate
(fig. 113, pos. 1).
z
Remove the condensate trap (fig. 113, pos. 2).
z
Fill the new condensate trap with water before
re-installing it.
z
Re-assemble the new condensate trap in reverse
order of disassembly.
z
Fit the casing.
z
Connect the heating system to the power supply,
insert the main fuse or switch on the circuit breaker.
z
Set the main switch on the BC10 to "1" (On).
14.28 Pressure sensor; replacing
z
Disconnect the heating system from the power
supply, remove the main fuse or switch off the circuit
breaker.
z
Set the main switch on the BC10 to "0" (Off).
z
Remove the casing.
z
Close the maintenance shut-off valves and drain the
Logamax plus GB142.
z
Remove the cable plug from the pressure sensor.
z
Loosen the pressure sensor by removing the
securing clip (see fig. 114).
z
Assemble the new pressure sensor and the plug in
reverse order of disassembly.
z
Fit the casing.
z
Connect the heating system to the power supply,
insert the main fuse or switch on the circuit breaker.
z
Set the main switch on the BC10 to "1" (On).
Fig. 113 Disconnecting the condensate trap connection
1
2
Fig. 114 Loosening the pressure sensor
NOTICE!
Fill and purge the Logamax plus GB142 as
required. See page 28.