Installation
6
6.4
Fitting the heating circuit supply and
return pipes
z
Fit a filling and drain cock in the heating system
supply pipe if required.
z
Also fit a safety valve in the system.
z
Thoroughly flush all pipes and radiators.
z
Refer to the installation template for the pipe connec-
tion dimensions.
z
Fit the compression fittings (fig. 9, pos. 1 and 2) first
to the Hydronic set (see fig. 10, 11 and 12) and then
to the appliance.
z
Connect the expansion tank to the system.
z
Connect the pipes so that they are free from strain.
Steel pipe
diameter
in inches
Equivalent length for Pipe Fittings in feet
Type of pipe fitting
90°-Elbow
Tee
(flow thru
branch)
Gate valve Gas cocks
Equivalent length in feet
¾
2.1
4.1
0.5
1.25
1
2.6
5.2
0.6
1.60
1 ¼
3.5
6.9
0.8
2.15
1 ½
4.0
8.0
0.9
2.50
Table 3
Equivalent length for pipe fittings in feet
Fig. 9
Pump manifold installation
pos. 1:
Compression fitting (heating system supply pipe)
pos. 2:
Compression fitting (heating system return pipe)
pos. 3:
DHW supply
pos. 4:
DHW return
pos. 5:
Relief valve
2
1
3
4
5
NOTICE
– Piping and components connected to the
water appliance for the space heating
application are suitable for use with potable
water.
– A water appliance which will be used to
supply potable water shall not be
connected to any heating system or
component(s) previously used with a
nonpotable water heating appliance.
NOTICE
– To protect the entire heating system we
recommend installing a dirt particle filter in
the return circuit. When connecting the
appliance to an existing heating system this
filter must definitely be installed.
– Install shut-off valves immediately before
and after the dirt particle filter to enable the
filter to be cleaned.
NOTICE
When using oxygen-permeable pipes, e. g. for
floor heating systems, you must separate the
system using heat exchangers.