Product information
Logamatic EMS RC35 programming unit - Subject to technical modifications
8
2
2.4
Specification
Temperature sensor characteristics
When measuring temperature sensors, observe the following requirements:
• Isolate the system before measuring.
• Measure the resistance at the cable ends.
• The resistances represent mean values and are subject to tolerances.
Unit
RC35
Power supply via BUS system
V
16 V DC
Power consumption
W
0.3
Power consumption with backlighting
W
0.6
Dimensions (width/height/depth)
mm
150/90/32
Weight
g
233
Operating temperature
°C
0 to +50
Storage temperature
°C
0 to +70
Relative humidity
%
0 to 90
CE designation
Tab. 2
Specification - RC35 programming unit
Outside temperature sensor
Flow temperature sensor
DHW temperature sensor
°C
k
Ω
°C
k
Ω
°C
k
Ω
– 20
96.358
10
19.872
60
2.490
– 15
72.510
16
15.699
65
2.084
– 10
55.054
20
12.488
70
1.753
– 5
42.162
25
10.001
75
1.481
0
32.556
30
8.060
80
1.256
5
25.339
35
6.535
85
1.070
10
19.872
40
5.331
90
0.915
15
15.699
45
4.372
95
0.786
20
12.488
50
3.606
100
0.677
25
10.001
55
2.989
30
8.060
Tab. 3
Resistances of the temperature sensors, for EMS only