Diagnosis
Logamatic EMS RC35 programming unit - Subject to technical modifications
44
7
7.3
Error message
You can use the
error message
menu to view the most recent faults in the fault memory, in order
to investigate a fault, for example.
Faults are categorised as follows:
•
current errors
are all unresolved faults currently present in the system. These can be one of the
following types:
locking
,
blocking
or
plant error
.
•
locking fault
1)
: Manually reset the heating system after the fault has been removed. For this,
press
RESET
on the boiler.
•
blocking fault
1)
: With blocking faults, the heating system continues to operate automatically,
as soon as the fault has been removed.
•
plant errors
relating to the heating system are logged in the RC35. Exceptions are boiler or
burner faults that are either “locking” or “blocking” faults. The heating system keeps operating as
much as possible during the fault; a reset is not required.
Burner operational
Heating demand
DHW demand
Flue gas test active
Service required / fault has occurred
Tab. 19 Explanation of the symbols for footnote 1), page 43
1) Not possible on boilers with UBA1.x, DBA or UBA-H3
For a list of the locking and blocking faults, which vary depending on the boiler, see the
installation and maintenance instructions for the boiler.
B
Turn rotary selector
to show the next message.