
Logamatic EMS RC35 programming unit - Subject to technical modifications
27
System settings (Service menu – Settings)
6
6.3
Heating circuit data
This chapter explains the settings for all heating circuits using heating circuit 1 as an example.
B
Turn rotary selector
anti-clockwise until
heating circuit 1
is selected.
B
Press
to select
heating circuit 1
.
The menu
SETTINGS\HTG. CIRC. 1
is opened.
Menu item
Input range
Factory
setting
Other information
Should heating circuit 1
be activated?
yes, no
yes
Which operating unit is
assigned to heating
circuit 1?
RC2x/RC20/RF,
RC35, none
RC35
See page 31.
For UBA1.x, RC2x is not available.
If “none” is selected, then the type of
control is changed over to “outside
temp. contr.” and is then hidden.
How should heating
circuit 1 be controlled?
outside temp.
contr.,
room temp.
controlled
outside
temp.
contr.
“room temp. controlled” can only be
set if RC2x or RC35 have been
assigned.
When selecting “room temp. control-
led” room flow will be used.
Which heating system
does heating circuit 1
have?
radiator,
convector,
floor
radiator
In case of HC1 setting “floor” only if
this concerns an oil/gas condensing
boiler. Additional heating circuits can
then be installed.
Use a safety thermostat with
underfloor heating systems.
Tab. 12 Navigator for service menu SETTINGS\HTG. CIRC. 1
SERVICE\SETTINGS
B
plant data
boiler data
domestic hot water
heating circuit 1