Logamatic EMS RC35 programming unit - Subject to technical modifications
37
System settings (Service menu – Settings)
6
DHW circulation
2)3)
Is a circulation pump
installed?
yes, no
no
How frequently should
the circul. pump be
switched on per hour?
once for 3 minutes,
twice for 3 minutes,
3 times for 3 minutes,
4 times for 3 minutes,
5 times for 3 minutes,
6 times for 3 minutes,
permanent operation
Twice for
3 minutes
switch on circ. pump
Graphical display of number of
times the pump is switched on
per hour.
Do you wish to change
the circulation switching
programme?
yes, no
no
When selecting “yes” the
system jumps to the DHW
circulation switching program.
Thermal disinfection
2)
Should a thermal
disinfection be carried
out?
yes, no
no
What temperature should
be used for thermal
disinfection?
60 °C to 80 °C
4)
70 °C
At temperatures above 60 °C
there is a risk of scalding at the
draw-off points during and after
thermal disinfection!
On which day should the
thermal disinfection be
performed?
Monday, Tuesday,
Wednesday,
Thursday, Friday,
Saturday, Sunday,
daily
Tuesday
At what time of day
should the th. disinfection
be performed?
0:00h to 23:00h
1:00h
Times entered must be whole
hours only (no minutes).
Menu item
Input range
Factory
setting
Other information
Tab. 14 Navigator for service menu SETTINGS\DHW