System settings (Service menu – Settings)
Logamatic EMS RC35 programming unit - Subject to technical modifications
40
6
6.6
RC35 calibration
B
Turn rotary selector
anti-clockwise, until
RC35 calibration
is selected.
B
Press
to select
RC35 calibration
.
Menu
SETTINGS\CALIB. RC35
opens.
Calibrating the displayed room temperature (calibration)
If there is a separate thermometer near the programming unit, it may show a different room
temperature to that shown on the programming unit. You can use this function to adjust (“calibrate”)
the programming unit to match the thermometer.
Before calibrating the room temperature, consider the following:
• Is the thermometer more accurate than the programming unit?
• Is the thermometer located close to programming unit so that they are both subject to the same
heat influences (e.g. sunlight, fireplace)?
Example: if the thermometer is showing a temperature 0.5 °C higher than the programming unit,
enter
+0.5 K
as the calibration value.
Menu item
Input range
Factory setting
Other
information
RC35 calibration
– 5.0 K to +5.0 K
0.0 K
Tab. 16 Navigator for service menu SETTINGS\CALIB. RC35
A thermometer may indicate temperature fluctuations more slowly or rapidly than the
programming unit.
B
Therefore, never calibrate the programming unit during phases when your heating
system is cooling down or heating up.
domestic hot water
heating circuit 1
solar data
RC35 calibration
SERVICE\SETTINGS
B