2.1 Selection keys
•
The front panel of the electronic control box has two LED displays showing the voltages
of the two power sources with their correspondent keys – (
A
) for Main line and (
B
) for
Secondary line – which allows to select the measurements.
•
The following keys: SET (
E
) - AUT (
F
) - MAN (
G
) - RESET (
H
) allow to select the operating
mode, which is indicated by the corresponding LED.
•
A mimic diagram is located at the center of the front panel; it shows the status of the
circuit breakers for load connection.
•
Two keys – (
C
) and (
D
) – can open and close the circuit breakers (buttons are active only
after pressing the MAN key).
A
B
E
F
G
H
C
D
2.2 Measurement selection
•
When the key located under each display (
A
) and (
B
) is pressed several times, it will be
possible to view the various measurements of the line sequentially.
•
Line-to-line voltages, line-to-neutral voltages (in case of single-phase lines) are available
for each line.
•
The combinations of the red LEDs indicate which measurement is selected. The list of
measurements may change depending on whether the electronic control box is set up for
the three-phase, two-phase or single-phase control.
•
After 1 minute without touching the key, the measurement returns to the default mea-
surement, which may be the first voltage line-to-line or the first voltage line-to-neutral,
depending on how the voltage control is set up.
•
In case of alarms or messages, the display will be occupied by the alarm code.
By pressing the selection key, it is possible to temporarily hide the alarm and access the
measurements.
2. Description of the
front panel
Example of a list of measurements
on an electronic control box set
up for a three-phase control.