The following messages can be displayed, at different moments:
Code Description
- - -
(Dashes) - The interlocking time is in progress.
They are displayed from the side in which the load is being transferred
Sta
(Start) - Indicates that the Start Generator command has been sent
Coo
(Cooling) - Indicates that the generator is being left running for the cooling
Tes
(Test) - When steady, it indicates that an off-load test - namely a power unit test
with the voltage controls active - is currently in progress
Tes
(Test) - When flashing, it indicates that an on-load test, namely an automatic net
failure simulation, is currently in progress
Loc
(Locked) - It indicates that the keyboard function one is trying to execute is
locked
8. Diagnostic
messages
•
When the unit is running, it is possible to verify a number of abnormal situations which are
signaled in different ways.
• Some alarms (tripped, withdrawn) have a dedicated LED which begins to flash when the
alarms go on.
• Other alarms are signaled through a code which consists of an A (alarm) and a number
indicating which alarm it is. This code will be flashing on one of the displays. If the code
refers to the main line branch, the alarm will be displayed on the left. Conversely, if the
code refers to the secondary line branch or if it is a generic alarm (e.g. battery), it will be
displayed on the right.
• When an alarm goes on, the red LED “ALARM” flashes in sync with the dedicated LED or
with the alarm code.
• The Global alarm relay output is de-energized during alarm conditions whereas it is
energized under normal conditions. If the unit does not operate due to a failure or power
supply problems, it will generate an alarm condition on its contact.
• Some alarms are automatically reset when the conditions generating them fail to work.
• Other alarms, described in the chart in the RIT column, are retentive, thus they are
stored.
• Once the alarm has been stored, the abnormal conditions must be eliminated in order to
be reset. Also, the operator must press the RESET key or send a special message via the
serial interface.