15
Setup
Description
Range
Default
P3.01
Minimum voltage threshold - release
70…98 % Ue
85 % Ue
P3.02
Minimum voltage threshold - retrieval
75…100 % Ue
90 % Ue
P3.03
Minimum voltage threshold delay
0.1 …. 900 s
1.0 s
P3.04
Maximum voltage threshold - release
102…120 % Ue / OFF
115 % Ue
P3.05
Maximum voltage threshold - retrieval
100…115 % Ue
110 % Ue
P3.06
Maximum voltage threshold delay
0.1 …. 900 s
1.0 s
P3.07
Threshold of phase failure
60 … 85% Ue / OFF
70 % Ue
P3.08
Phase failure threshold delay
0.1 … 30.0 s
0.1 s
P3.09
Voltage unbalance threshold
1 … 20 % / OFF
10 %
P3.10
Voltage unbalance threshold delay
0.1 … 900 s
5.0 s
P3.11
Threshold of minimum frequency
99 … 80 % Fe / OFF
95 % Fe
P3.12
Minimum frequency threshold delay
0.1 … 900 s
5.0 s
P3.13
Threshold of maximum frequency
101 … 120% Fe / OFF
105 % Fe
P3.14
Maximum frequency threshold delay
0.1 … 900 s
3.0 s
P3.15
Voltage delay of secondary line within
the limits
1 … 3600 s
20 s
Note:
For explanations on the
operation of parameters, see
previous page concerning the
main line menu
Programmable input functions
Function Description
Notes
OFF
OFF
Input not used
For
Forced changeover on secondary line
When closed, it forces the changeover on the
secondary line even if main line voltage is within
the limits. Re-commutation occurs on the main
line when the input is released or in case the
secondary line voltage is not within the limits
IN.R
Inhibition return on main line
In automatic mode, when closed, it blocks
the automatic return on the main line after the
main line voltage has returned within the limits.
It is used for preventing the second power
cutoff, due to the re-transferal, from occurring
automatically in an unexpected moment
S.GE
Generator voluntary Start/stop
In automatic mode, when closed, it starts up
the generator
EME
Emergency
NC contact which, if opened, opens both circuit
breakers and generates an alarm
G.rE
Generator ready
If closed, it refers to a Generator in automatic
mode and not in alarm mode.
If opened, it generates an alarm code
Loc
Keyboard total lock
If closed, it locks all keyboard functions except
for measurement views
L.PA
Lock parameter access
If closed, it locks the access to setups
7.6 P3 menu - Secondary line voltage control
Setup
Description
Range
Default
P4.01
Programmable input function 1
See list
“Programmable
input functions”
For
Forced changeover
on secondary line
P4.02
Programmable input function 2
In.r
inhibition return
on main line
7.7 P4 menu - Programmable inputs
The highlighted param-
eters are included only in
version M7000CB/EVO