![Bticino M7000CB Manual Download Page 19](http://html1.mh-extra.com/html/bticino/m7000cb/m7000cb_manual_2825202019.webp)
19
Mors.
Function
1
Main line circuit breaker opening
2
Common main line commands
3
Main line circuit breaker closing
4
Secondary line circuit breaker opening
5
Common secondary line commands
6
Secondary line circuit breaker closing
7
Programmable relay 1
(Default function = Start/Stop generator)
8
Common programmable relay 1
9
Common programmable relay 2
10
Programmable relay 2/NO
(Default function = Unit ready)
11
Programmable relay 2/NC
(Default function = Unit ready)
12
Common programmable relay 3
13
Programmable relay 3/NO
(Default function = Global alarm -
closed when ok)
14
Programmable relay 3/NC
(Default function = Global alarm)
15
AUX input of Main line circuit breaker
Mors.
Function
16
AL input of Main line circuit breaker
17
DISCONNECTED input of Main line circuit
breaker
18
AUX input of Secondary line circuit breaker
19
AL input of Secondary line circuit breaker
20
DISCONNECTED input of Secondary line
circuit breaker
21
Programmable input 1
(Default = Forcing on secondary line)
22
Programmable input 2
(Default = Inhibition return on main line)
23
+ VDC supply
24
– VDC supply
25
Common for inputs (from 15 to 22)
26
AC supply
27
AC supply
MAIN
L1 L2
L3 N
Main line three-phase measurement input
SEC.
L1 L2
L3 N
Secondary line three-phase
measurement input
10. Connections