![Bticino M7000CB Manual Download Page 20](http://html1.mh-extra.com/html/bticino/m7000cb/m7000cb_manual_2825202020.webp)
Electronic Control Box
20
Auxiliary power supply
DC power supply operating limits
9...70VDC (Us=12-24-48VDC)
AC power supply operating limits
187…264VAC (Us=220…240VAC)
Frequency
45…65Hz
Max. absorbed power
6VA (Us=240VAC)
Max. dissipated power
4,8W (Us= 240VAC or Us=48VDC)
Max. absorbed current
420mA to 12VDC; 200mA to 24VDC; 100mA to 48VDC
Micro-breaking immunity time
50ms
Voltage inputs
Max. rated voltage (Ue)
690VAC phase-phase (400VAC phase-neutral)
UL usage data
600VAC phase-phase (340VAC phase-neutral)
Measuring range
80…800VAC phase--phase
Frequency range
45…65Hz
Type of measurement
TRMS (true effective value)
Measurement input impedance
>1,1M
Ω
phase-phase and >0,5M
Ω
phase-neutral
Type of connection
One, two or three phase
Measurement error
Class 0,5 ±0,25% f.s. ±1digit
Digital inputs
Type of input
Negative
Input current
≤
10mA
Input current “0” state
≤
1,5 (typical 2,9V)
Input current “1” state
≥
5,3 (typical 4,3V)
Input signal delay
≥
50msec
Relay outputs terminals 1-2 and 4-5
Type of contact
1 NO
Nominal range at 250VAC
12A
Contact nominal range
16A in AC1 250V - B300
Maximum current on terminal 1.2
12A
Relay outputs terminals 2-3 and 5-6
Type of contact
1 NO
Contact nominal range
8A in AC1 250V - B300
30VDC 1A Auxiliary service supply
Maximum current on terminal 2.2
12A
Relay outputs terminals 7-8
Type of contact
1 NO
Contact nominal range
8A in AC1 250V - B300
30VDC 1A Auxiliary service supply
Relay outputs terminals 9-10-11 and 12-13-14
Type of contact
1 change-over contact
Contact nominal range
8A in AC1 250V - B300
30VDC 1A Auxiliary service supply
Communication interfaces
RS232 serial interface
Programmable Baud-rate 1200…38400 bps
Connection via RJ6/6 connector
RS485 serial interface
(COM only)
Isolated with programmable Baud-rate
1200…38400 bps
Connection via removable terminals
Insulation
Rated insulation Voltage (Ui)
690V
Environmental operating conditions
Operating temperature
-20…+60°C
Temperature
-30…+80°C
Relative humidity
<
90%
Maximum Pollution degree
Degree 3
Overvoltage category
3
Connections
Type of terminal
Removable
Conductor section (min. and max.)
0,2…2,5 mmq (24÷12 AWG)
Tightening torque
0,5 Nm (4,5 LBin)
Housing
Material
Thermoplastic LEXAN 3412R
Version
Flush mounting
Dimensions L x H x D
144 x 144 x 94mm
Protection degree
IP41 on front, IP20 on back
Weight
950g
Certifications and compliance
Certifications and compliance:
IEC/EN 61010-1, IEC/EN 61000-6-2, CISPR 11/EN 55011, IEC/EN 61000-3-2, IEC/EN 61000-3-3,
IEC/EN 60068-2-61, IEC/EN 60068-2-27, IEC/EN 60068-2-6, UL508 C22.2-N°14-95
11. Technical
features
Summary of Contents for M7000CB
Page 1: ...Electronic Control Box item M7000CB item M7000CB EVO Part Y1791C 10 08 01 PC ...
Page 2: ......
Page 41: ......