13
Setup
Description
Range
Default
P1.01
Type of application
U-G
= Utility-to-Generator
U-U
= Utility-to-Utility
U-G
P1.02
Control of phase sequence
OFF
- Disabled
123
- Direct
321
- Opposite
OFF
P1.03
Changeover control
FEE
- With feedback
NOF
- Without feedback
FEE
P1.04
Circuit breakers Timeout
OFF / 1…900s
5 s
P1.05
Enable control of withdrawn
OFF
(Control disabled)
ON
(Control enabled)
OFF
P1.06
Maximum time load not powered
(A07 alarm delay)
OFF / 1…3600s
OFF
P1.07
Startup delay time, generator
0 …. 900 s
1 s
P1.08
Cooling time, generator
1…3600s
120 s
P1.09
Minimum battery voltage threshold
OFF / 70…100%
75%
P1.10
Maximum battery voltage threshold
OFF / 110…140%
130%
P1.11
Battery threshold delay time
0…60 s
10 s
P1.01
Determines the type of commutation (utility-to-utility/ utility-to-generator)
P1.04
If, after sending an opening or closing command to a switch, it does not place itself correctly
within this time, the A03 or A04 alarms will be generated
P1.05
Enable the control only if their contacts are wired
P1.06
If both sources are simultaneously unavailable in automatic mode for a period of time longer
than P2.09, the A07 alarm will be generated
P1.07
Time between the line failure used below and transmission of the startup signal to the generator
on the secondary line.
It is a time which is independent from the circuit breaker opening time
P1.08
Time whereby the generator is left in operation in order to cool down after being disconnected
from the load
7.4 P1 menu - General data
The highlighted param-
eters are included only in
versionM7000CB/EVO