NOTE:
Proper polarity must be maintained for 115-v wiring. If
polarity is incorrect, control board fault code indicator light will
flash rapidly and the furnace will not operate.
B.
24-v Wiring
Make field 24-v connections at the 24-v terminal strip. (See Fig.
10.) Connect terminal Y as shown in Fig. 9 for proper cooling
operation. Use only AWG No. 18, color-coded, copper thermostat
wire.
The 24-v circuit contains an automotive-type, 3-amp fuse located
on the main control board. Any direct shorts during installation,
service, or maintenance could cause this fuse to blow. If fuse
replacement is required, use ONLY a 3-amp fuse of identical size.
C.
Accessories
1. Electronic Air Cleaner (EAC)
Two quick-connect terminals, marked EAC-1 and EAC-2
are provided for EAC connection. These terminals are
energized with 115-v, (1.0-amp maximum) during blower
motor operation.
2. Humidifier (HUM)
Quick-connect terminal HUM and screw terminal C
OM
-24V
are provided for 24-v humidifier connection. The terminals
are energized with 24-v 0.5-amp maximum after inducer
motor prepurge period.
WARNING:
DO NOT connect furnace control HUM
terminal to HUM (humidifier) terminal on Thermidis-
tat™, Zone Controller, or similar device. See Thermidis-
tat, Zone Controller, thermostat, or controller manufac-
turer’s instructions for proper connection. A failure to
follow this warning could result in fire.
NOTE:
A field-supplied, 115-v controlled relay connected to
EAC terminals may be added if humidifier operation is desired
during blower operation.
TABLE 5—ELECTRICAL DATA
UNIT SIZE
VOLTS—
HERTZ—
PHASE
OPERATING
VOLTAGE RANGE
MAXIMUM
UNIT AMPS
MINIMUM
WIRE GAGE
MAXIMUM
WIRE LENGTH (FT)‡
MAXIMUM FUSE OR
CKT BKR
AMPS†
Maximum*
Minimum*
024045
115—60—1
127
104
6.0
14
47
15
036045
115—60—1
127
104
8.3
14
34
15
024070
115—60—1
127
104
5.9
14
47
15
036070
115—60—1
127
104
8.7
14
32
15
042091
115—60—1
127
104
9.0
14
31
15
048091
115—60—1
127
104
10.4
14
27
15
036110
115—60—1
127
104
8.0
14
35
15
048111
115—60—1
127
104
10.1
14
28
15
060111
115—60—1
127
104
14.4
12
31
20
048135
115—60—1
127
104
10.1
14
28
15
060135
115—60—1
127
104
13.3
12
33
20
060155
115—60—1
127
104
14.0
12
31
20
* Permissible limits of the voltage range at which the unit operates satisfactorily. † Time-delay type is recommended.
‡ Length shown is as measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop.
Fig. 9—Heating and Cooling Application Wiring Diagram
A98521
115-V FIELD-
SUPPLIED
DISCONNECT
AUXILIARY
J-BOX
24-V
TERMINAL
BLOCK
THREE-WIRE
HEATING-ONLY
FIVE WIRE
NOTE 1
NOTE 2
FIELD-SUPPLIED
DISCONNECT
CONDENSING
UNIT
TWO
WIRE
FURNACE
C
O
N
T
R
O
L
R
G
C
W
C
R
G
Y
GND
GND
FIELD 24-V WIRING
FIELD 115-, 208/230-, 460-V WIRING
FACTORY 24-V WIRING
FACTORY 115-V WIRING
208/230- OR
460-V
THREE
PHASE
208/230-V
SINGLE
PHASE
BLOWER DOOR SWITCH
WHT
BLK
WHT
BLK
NOTES:
Connect Y-terminal in furnace as shown for proper blower operation.
Some thermostats require a "C" terminal connection as shown.
If any of the original wire, as supplied, must be replaced, use
same type or equivalent wire.
W
Y
GND
THERMOSTAT
TERMINALS
1.
2.
3.
—9—
Summary of Contents for GAS-FIRED INDUCED-COMBUSTION FURNACES 383KAV
Page 19: ...19...