background image

a. Determine natural gas orifice size and manifold pressure

for correct input.

(1.) Obtain average yearly gas heat value (at installed

altitude) from local gas supplier.

(2.) Obtain average yearly gas specific gravity from

local gas supplier.

(3.) Verify furnace model. Table 6 can only be used for

model 383KAV Furnaces.

(4.) Find installation altitude in Table 6.

NOTE:

For Canada altitudes of 2000 to 4500 ft, use U.S.A.

altitudes of 2001 to 3000 ft in Table 6.

(5.) Find closest natural gas heat value and specific

gravity in Table 6.

(6.) Follow heat value and specific gravity lines to point

of intersection to find orifice size and manifold
pressure settings for proper operation .

EXAMPLE: (0—2000 ft altitude)
Heating value = 1025 Btu/cu ft
Specific gravity = 0.62
Therefore: Orifice No. 43*

Manifold pressure 3.3-in. wc

* Furnace is shipped with No. 43 orifices. In this example
all main burner orifices are the correct size and do not need
to be changed to obtain proper input rate.

(7.) Check and verify burner orifice size in furnace.

NEVER ASSUME ORIFICE SIZE. ALWAYS
CHECK AND VERIFY.

b. Adjust manifold pressure to obtain input rate.

(1.) Remove regulator adjustment seal cap. (See Fig.

12.)

(2.) Turn adjusting screw, counterclockwise (out) to

decrease manifold pressure or clockwise (in) to
increase manifold pressure.

NOTE:

This furnace has been approved for a manifold pressure

of 3.2-in. wc to 3.8-in. wc when installed at altitudes up to 2000 ft.
For altitudes above 2000 ft, the manifold pressure can be adjusted
from 2.0-in. wc to 3.8-in. wc.

CAUTION:

DO NOT bottom out gas valve regulator

adjusting screw. This can result in unregulated manifold
pressure and result in excess overfire and heat exchanger
failures.

NOTE:

If orifice hole appears damaged or it is suspected to have

been redrilled, check orifice hole with a numbered drill bit of
correct size. Never redrill an orifice. A burr-free and squarely
aligned orifice hole is essential for proper flame characteristics.

(3.) After correct manifold pressure is obtained, replace

gas valve regulator adjustment screw cap and verify
adjusted gas input rate using method outlined in
item c.

(4.) Burner flame should be clear blue, almost transpar-

ent. (See Fig. 13.)

c. Verify natural gas input rate by clocking gas meter.

NOTE:

High-Altitude Adjustment

UNITED STATES

At installation altitudes above 2000 ft, this furnace has been
approved for a 4 percent derate for each 1000 ft above sea level.
See Table 7 for derate multiplier factor.

EXAMPLE:
88,000 Btuh input furnace installed at 4300 ft.

Furnace Input

Rate at

Sea Level

X

Derate

Multiplier

Factor

=

Furnace Input Rate

at Installation Altitude

88,000

X

0.82

=

72,160

CANADA

At installation altitudes from 2000 to 4500 ft, this furnace must be
derated 10 percent by an authorized Gas Conversion Station. To
determine correct input rate for altitude, see example above and
use 0.90 as derate multiplier factor.

a. Turn off all other gas appliances and pilots.

b. Start furnace and let operate for 3 minutes.

c. Measure time (in sec) for gas meter test dial to complete

1 revolution.

d. Refer to Table 8 for cu ft of gas per hr.

e. Multiply gas rate (cu ft/hr) X heating value (Btu/cu ft)

using natural gas heating value from local gas
utility/supplier.

EXAMPLE: (0—2000 ft altitude)
Btuh input from rating plate = 110,000 Btuh
Btu heating input = Btu/cu ft X cu ft/hr
Heating value of gas = 1050 Btu/cu ft
Time for 1 revolution of 2-cu ft dial = 70 sec
Gas rate = 103 cu ft/hr (from Table 8)
Btu heating input = 103 X 1050 = 108,150 Btuh
In this example, the orifice size and manifold pressure
adjustment is within

±

2 percent of the furnace input rate.

2. Set temperature rise.

Furnace must operate within range of temperature rise
specified on the furnace rating plate. Determine the air
temperature rise as follows.

a. Place duct thermometers in return and supply ducts as

near furnace as possible. Be sure thermometers do not
"see" heat exchangers so that radiant heat will not affect
thermometer readings. This is particularly important
with straight-run ducts.

b. When thermometer readings stabilize, subtract return-air

temperature from supply-air temperature to determine
temperature rise.

c. Adjust air temperature rise by adjusting blower speed.

Increase blower speed to reduce temperature rise. De-
crease blower speed to increase temperature rise.

WARNING:

Disconnect the electrical power before

changing the speed tap. A failure to follow this warning
can cause personal injury.

d. To change blower motor speed selections for heating

mode, remove blower motor lead from control HEAT
terminal. (See Fig. 10.) Select desired blower motor
speed lead from 1 of the other terminals and relocate it
to HEAT terminal. See Table 9 for lead color identifi-
cation. Reconnect unused lead on SPARE terminal.

—13—

Summary of Contents for GAS-FIRED INDUCED-COMBUSTION FURNACES 383KAV

Page 1: ...unit and other safety precautions that may apply In the United States follow all safety codes including the National Fuel Gas Code NFGC NFPA 54 1999 ANSI Z223 1 1999 and the Installation Standards Wa...

Page 2: ...4 3 16 12 9 16 12 11 16 4 127 042091 17 1 2 15 7 8 16 4 124 048091 21 19 3 8 19 1 2 4 155 036110 17 1 2 15 7 8 16 4 153 048111 21 19 3 8 19 1 2 4 173 060111 24 1 2 22 7 8 23 4 176 048135 21 19 3 8 19...

Page 3: ...g codes installation must conform with NFGC in the United States and the NSCNGPIC and all authorities having jurisdiction in Canada These instructions cover minimum requirements for a safe instal lati...

Page 4: ...s warning can cause a fire personal injury or death This furnace must be installed so the electrical components are protected from water This furnace shall not be installed directly on carpeting tile...

Page 5: ...cating with the outdoors shall be provided See item 2 below c If furnace is installed on a raised platform to provide a return air plenum and return air is taken directly from hallway or space adjacen...

Page 6: ...VENT THROUGH ROOF 1 SQ IN PER 1000 BTUH IN DOOR OR WALL 12 MAX 1 SQ IN PER 1000 BTUH IN DOOR OR WALL 12 MAX INTERIOR HEATED SPACE Minimum opening size is 100 sq in with minimum dimensions of 3 in Mini...

Page 7: ...t in hole Install flat washer if desired 3 Install another nut on other side of furnace base Install flat washer if desired 4 Adjust outside nut to provide desired height and tighten inside nut to sec...

Page 8: ...15 v Wiring Refer to the furnace rating plate or Table 5 for equipment electrical requirements The control system requires an earth ground for proper operation CAUTION Do not connect aluminum wire bet...

Page 9: ...if humidifier operation is desired during blower operation TABLE 5 ELECTRICAL DATA UNIT SIZE VOLTS HERTZ PHASE OPERATING VOLTAGE RANGE MAXIMUM UNIT AMPS MINIMUM WIRE GAGE MAXIMUM WIRE LENGTH FT MAXIMU...

Page 10: ...ontrol area The switch or fuse link opens and shuts off power to the gas valve if a flame rollout or overheating condition occurs in the gas control area DO NOT bypass the switch Correct inadequate co...

Page 11: ...NDUCTOR ON PCB FIELDWIRINGTERMINAL FIELD GROUND EQUIPMENT GROUND FIELD SPLICE PLUG RECEPTACLE L1 L2 L1 BLWR HI LO TO 115VAC FIELD DISCONNECT NOTE 4 EQUIPMENT GROUND SPARE 2 HEAT SPARE 1 COOL NOTE 7 CO...

Page 12: ...e blower if it was off and begins a heating cycle The blower remains on until the end of the prepurge period then shuts off until the end of the hot surface igniter warm up and trial for ignition peri...

Page 13: ...TED STATES At installation altitudes above 2000 ft this furnace has been approved for a 4 percent derate for each 1000 ft above sea level See Table 7 for derate multiplier factor EXAMPLE 88 000 Btuh i...

Page 14: ...3 3 0 43 3 1 43 3 2 43 3 3 Altitudes 950 43 2 7 43 2 8 43 2 9 43 3 0 43 3 1 2000 975 43 2 6 43 2 7 43 2 8 43 2 9 43 2 9 to 1000 43 2 5 43 2 5 43 2 6 43 2 7 43 2 8 4500 1025 43 2 3 43 2 4 43 2 5 43 2 6...

Page 15: ...50 43 2 5 43 2 6 43 2 7 43 2 8 43 2 9 to 775 43 2 4 43 2 5 43 2 5 43 2 6 43 2 7 800 43 2 2 43 2 3 43 2 4 43 2 5 43 2 5 7000 825 43 2 1 43 2 2 43 2 2 43 2 3 43 2 4 850 48 3 7 43 2 0 43 2 1 43 2 2 43 2...

Page 16: ...48 3 4 775 49 3 3 49 3 4 49 3 5 49 3 6 49 3 7 Orifice sizes shown in BOLD are factory installed CAUTION DO NOT redrill orifices Improper drilling burrs out of round holes etc can cause excessive burn...

Page 17: ...ower to furnace d Set thermostat to call for heat and wait 1 minute When pressure switch is functioning properly hot surface igniter should NOT glow and control diagnostic light flashes a status code...

Page 18: ..._________ 1 4 in Upward Slope ____________ Joints Secure ____________ See Attached Vent Table Instructions CHECKLIST START UP ____________ Gas Input Rate Set Within 2 percent of Rating Plate _________...

Page 19: ...19...

Page 20: ...ideo based formats and materials All include video and or slides plus companion book Classroom Service Training plus hands on the products in our labs can mean increased confidence that really pays di...

Reviews: