background image

CAUTION:

Air for combustion must not be contami-

nated by halogen compounds, which include fluoride,
chloride, bromide, and iodide. These elements are found
in aerosol sprays, detergents, bleaches, cleaning solvents,
salts, air fresheners, and other household products.

All fuel-burning equipment must be supplied with air for combus-
tion of the fuel. Sufficient air MUST be provided to ensure there
will not be a negative pressure in the equipment room or space. In
addition, a positive seal MUST be made between the furnace
cabinet and the return-air duct to prevent pulling air from the
burner area and blocked vent safeguard opening.

CAUTION:

The operation of exhaust fans, kitchen ven-

tilation fans, clothes dryers, or fireplaces could create a
NEGATIVE PRESSURE CONDITION at the furnace.
Make-up air MUST BE PROVIDED for the ventilation
devices, in addition to that required by the furnace.

The requirements for combustion and ventilation air depend upon
whether the furnace is located in an unconfined or confined space.

A.

Unconfined Space

An unconfined space must have at least 50 cubic ft for each 1000
Btuh of input for all the appliances (such as furnaces, clothes
dryer, water heaters, etc.) in the space.

If the unconfined space is of unusually tight construction, air for
combustion and ventilation MUST come from either the outdoors
or spaces freely communicating with the outdoors. Combustion
and ventilation openings must be sized the same as for a confined
space as defined below. Return air must not be taken from the
room unless an equal or greater amount of air is supplied to the
room.

B.

Confined Space

A confined space is defined as a space whose volume is less than
50 cu ft per 1000 Btuh of total input ratings of all appliances
installed in that space. A confined space MUST have provisions
for supplying air for combustion, ventilation, and dilution of flue
gases using 1 of the following methods. (See Fig. 3, 4 and Table
2.)

NOTE:

In determining free area of an opening, the blocking

effect of louvers, grilles, and screens must be considered. If free
area of louver or grille design is unknown, assume that wood
louvers have a 20 percent free area and metal louvers or grilles
have a 60 percent free area. Screens, when used, must not be
smaller than 1/4-in. mesh. Louvers and grilles must be constructed
so they cannot be closed.

The size of the openings depends upon whether air comes from
outside of the structure or an unconfined space inside the structure.

1. All air from inside the structure requires 2 openings (for

structures not usually tight):

a. Each opening MUST have at least 1 sq in. of free area

per 1000 Btuh of total input for all equipment within the
confined space, but not less than 100 sq in. per opening.
(See Fig. 3 and Table 2.) The minimum dimension of air
openings shall not be less than 3 in.

b. If building is constructed unusually tight, a permanent

opening directly communicating with the outdoors shall
be provided. See item 2 below.

c. If furnace is installed on a raised platform to provide a

return-air plenum, and return air is taken directly from
hallway or space adjacent to furnace, all air for combus-
tion must come from outdoors.

2. Air from outside the structure requires 1 of the following

methods:
a. If combustion air is taken from outdoors through 2

vertical ducts, the openings and ducts MUST have at
least 1 sq in. of free area per 4000 Btuh of total input for
all equipment within the confined space. (See Fig. 4 and
Table 2.)

b. If combustion air is taken from outdoors through 2

horizontal ducts, the openings and ducts MUST have at
least 1 sq in. of free area per 2000 Btuh of total input for
all equipment within the confined space. (See Fig. 4 and
Table 2.)

c. If combustion air is taken from outdoors through a single

opening or duct (horizontal or vertical) commencing
within 12 in. of the top of the confined space, opening
and duct MUST have at least 1 sq in. of free area per
3000 Btuh of the total input for all equipment within the
confined space and not less than the sum of the areas of
all vent connectors in the confined space. (See Fig. 4 and
Table 2.) Equipment clearances to the structure shall be
at least 1 in. from the sides and back and 6 in. from the
front of the appliances.

When ducts are used, they must be of the same cross-sectional area
as the free area of the openings to which they connect. The
minimum dimension of ducts must not be less than 3 in. (See Fig.
4.)

AIR DUCTS

I.

GENERAL REQUIREMENTS

The duct system should be designed and sized according to
accepted national standards such as those published by: Air
Conditioning Contractors Association (ACCA), Sheet Metal and
Air Conditioning Contractors National Association (SMACNA) or
American Society of Heating, Refrigerating and Air Conditioning
Engineers (ASHRAE). Or consult factory The Air Systems Design
Guidelines 
reference tables available from your local distributor.
The duct system should be sized to handle the required system
design airflow CFM at the design external static pressure.
When a furnace is installed so that the supply ducts carry air to
areas outside the space containing the furnace, the return air must
also be handled by a duct(s) sealed to the furnace casing and
terminating outside the space containing the furnace.
Secure ductwork with proper fasteners for type of ductwork used.
Seal supply- and return-duct connections to furnace with code
approved tape or duct sealer.
Flexible connections should be used between ductwork and
furnace to prevent transmission of vibration. Ductwork passing
through unconditioned space should be insulated to enhance
system performance. When air conditioning is used, a vapor
barrier is recommended.
Maintain a 1-in. clearance from combustible materials to supply air
ductwork for a distance of 36 in. horizontally from the furnace. See
NFPA 90B or local code for further requirements.

For Example:

383KAV FURNACE

INPUT BTUH

MINIMUM SQ FT WITH

7-1/2 FT CEILING

44,000

293

66,000

440

88,000

587

110,000

733

132,000

880

154,000

1026

—5—

Summary of Contents for GAS-FIRED INDUCED-COMBUSTION FURNACES 383KAV

Page 1: ...unit and other safety precautions that may apply In the United States follow all safety codes including the National Fuel Gas Code NFGC NFPA 54 1999 ANSI Z223 1 1999 and the Installation Standards Wa...

Page 2: ...4 3 16 12 9 16 12 11 16 4 127 042091 17 1 2 15 7 8 16 4 124 048091 21 19 3 8 19 1 2 4 155 036110 17 1 2 15 7 8 16 4 153 048111 21 19 3 8 19 1 2 4 173 060111 24 1 2 22 7 8 23 4 176 048135 21 19 3 8 19...

Page 3: ...g codes installation must conform with NFGC in the United States and the NSCNGPIC and all authorities having jurisdiction in Canada These instructions cover minimum requirements for a safe instal lati...

Page 4: ...s warning can cause a fire personal injury or death This furnace must be installed so the electrical components are protected from water This furnace shall not be installed directly on carpeting tile...

Page 5: ...cating with the outdoors shall be provided See item 2 below c If furnace is installed on a raised platform to provide a return air plenum and return air is taken directly from hallway or space adjacen...

Page 6: ...VENT THROUGH ROOF 1 SQ IN PER 1000 BTUH IN DOOR OR WALL 12 MAX 1 SQ IN PER 1000 BTUH IN DOOR OR WALL 12 MAX INTERIOR HEATED SPACE Minimum opening size is 100 sq in with minimum dimensions of 3 in Mini...

Page 7: ...t in hole Install flat washer if desired 3 Install another nut on other side of furnace base Install flat washer if desired 4 Adjust outside nut to provide desired height and tighten inside nut to sec...

Page 8: ...15 v Wiring Refer to the furnace rating plate or Table 5 for equipment electrical requirements The control system requires an earth ground for proper operation CAUTION Do not connect aluminum wire bet...

Page 9: ...if humidifier operation is desired during blower operation TABLE 5 ELECTRICAL DATA UNIT SIZE VOLTS HERTZ PHASE OPERATING VOLTAGE RANGE MAXIMUM UNIT AMPS MINIMUM WIRE GAGE MAXIMUM WIRE LENGTH FT MAXIMU...

Page 10: ...ontrol area The switch or fuse link opens and shuts off power to the gas valve if a flame rollout or overheating condition occurs in the gas control area DO NOT bypass the switch Correct inadequate co...

Page 11: ...NDUCTOR ON PCB FIELDWIRINGTERMINAL FIELD GROUND EQUIPMENT GROUND FIELD SPLICE PLUG RECEPTACLE L1 L2 L1 BLWR HI LO TO 115VAC FIELD DISCONNECT NOTE 4 EQUIPMENT GROUND SPARE 2 HEAT SPARE 1 COOL NOTE 7 CO...

Page 12: ...e blower if it was off and begins a heating cycle The blower remains on until the end of the prepurge period then shuts off until the end of the hot surface igniter warm up and trial for ignition peri...

Page 13: ...TED STATES At installation altitudes above 2000 ft this furnace has been approved for a 4 percent derate for each 1000 ft above sea level See Table 7 for derate multiplier factor EXAMPLE 88 000 Btuh i...

Page 14: ...3 3 0 43 3 1 43 3 2 43 3 3 Altitudes 950 43 2 7 43 2 8 43 2 9 43 3 0 43 3 1 2000 975 43 2 6 43 2 7 43 2 8 43 2 9 43 2 9 to 1000 43 2 5 43 2 5 43 2 6 43 2 7 43 2 8 4500 1025 43 2 3 43 2 4 43 2 5 43 2 6...

Page 15: ...50 43 2 5 43 2 6 43 2 7 43 2 8 43 2 9 to 775 43 2 4 43 2 5 43 2 5 43 2 6 43 2 7 800 43 2 2 43 2 3 43 2 4 43 2 5 43 2 5 7000 825 43 2 1 43 2 2 43 2 2 43 2 3 43 2 4 850 48 3 7 43 2 0 43 2 1 43 2 2 43 2...

Page 16: ...48 3 4 775 49 3 3 49 3 4 49 3 5 49 3 6 49 3 7 Orifice sizes shown in BOLD are factory installed CAUTION DO NOT redrill orifices Improper drilling burrs out of round holes etc can cause excessive burn...

Page 17: ...ower to furnace d Set thermostat to call for heat and wait 1 minute When pressure switch is functioning properly hot surface igniter should NOT glow and control diagnostic light flashes a status code...

Page 18: ..._________ 1 4 in Upward Slope ____________ Joints Secure ____________ See Attached Vent Table Instructions CHECKLIST START UP ____________ Gas Input Rate Set Within 2 percent of Rating Plate _________...

Page 19: ...19...

Page 20: ...ideo based formats and materials All include video and or slides plus companion book Classroom Service Training plus hands on the products in our labs can mean increased confidence that really pays di...

Reviews: