46
6.3.7.2.
Zone Offsets
This option allows actual temperature offset for each zone, allowing calibration (or
deliberate miscalibration) of each sensor. Use the Left (<) or Right (>) buttons to
change the zone. After the selection is made, touch
SAVE
.
S
Temperature Offset:
Adjustable between --5 to 5
_
F (--3 to 3
_
C)
d
Default = 0
_
F
6.3.7.3.
Zone Airflow Limits
Since a bypass damper is prohibited in this system, this setting is used to select the
maximum allowable noise/airflow relationship into each zone based on air noise
and comfort requirements.
LOW
means 100% of maximum assessed airflow;
MED--LOW
means 138% of maximum assessed airflow;
MEDIUM
means 176%
of maximum assessed airflow;
MED--HIGH
means 214% of maximum assessed
airflow;
HIGH
means 250% of maximum assessed airflow; and
NO LIMIT
means
the equipment does not stage down.
CFM associated for each limit is shown on the screen. Compare this value with the
equipment’s low stage CFM value to ensure that equipment will run for each zone.
Assessed airflow is determined as described in
DUCT ASSESSMENT
.
After the selections are made, touch
SAVE
.
S
Touch the zone name that you wish to change
S
Select the zone to adjust airflow:
Low, Med--Low, Medium, Med--High, High,
or No Limit
d
Default = High
6.3.7.4.
Duct Assessment Time
This option allows the installer to select the time in which the duct assessment will
be performed. After the selection is made, touch
SAVE
.
Summary of Contents for Evolution Connex SYSTXBBECC01-A
Page 2: ......
Page 10: ......
Page 95: ...85 R G FE Fan Coil or Variable Speed Furnace A07114 G Input Wiring for Blower Operation ...
Page 96: ...86 R G FE Fan Coil or Variable Speed Furnace A07115 G Input Wiring for System Shutdown ...
Page 97: ...87 NOTES ...
Page 98: ...88 NOTES Cont ...
Page 99: ......