31
After the selections are made, touch
SAVE
.
S
Cooling Airflow:
Quiet, Comfort, EFF325, EFF350, or Max
d
Default = Comfort
S
Dehumidify Airflow:
Normal or High
d
Default = Normal
6.3.2.2.
Altitude
S
Static Pressure selection:
0 to 10,000 feet. This is used to correct the static
pressure readings the system performs.
6.3.2.3.
Fan Coil Dehumidification
The Dehum Drain Time option turns off the continuous fan at the end of cooling for
five minutes in order to drain the indoor coil of water. The fan will only be turned
off if a dehumidify demand existed at the start of or during the cooling cycle.
The Electric Reheat option enables the electric heat to be used while
cool--to--dehumidify is running. This will allow the cool--to--dehumidify function to
run longer, greatly improving humidity control in cooling mode. Accumulated
electrical energy used while reheating (in kilowatt--hours) is shown on the Fan Coil
Run Hours screen and can be reset there. This option is only available with fan coil
systems.
After the selections are made, touch
SAVE
.
S
Dehum Drain Time:
Adjustable from 5 to 60 minutes or OFF
d
Default = 15 minutes
S
Electric Reheat:
Yes or No
d
Default = No