50
A12194
S
Airflow:
Selectable from Off to Max in 50 CFM increments
d
Off = 450 CFM, MAX = (odu_size in KBTU * 400) / 12)
d
Default = Off
NOTE
: Selected airflow used during hydronic heating is a fixed value, it does not
vary.
S
Blower On Delay:
Selectable from 0 to 240 seconds
d
Default = 30 seconds
S
Blower Off Delay:
Selectable from 0 to 240 seconds
d
Default = 0 seconds
6.4.
Check out
Touch
CHECKOUT
to view the equipment installed in the system. Perform
checkout test to make sure each piece of equipment is operating properly.