49
6.3.9.
Utility Curtailment
Utility Saver is used to force the equipment to a lower stage (low or off) when
activated by the utility company, typically during peak load times. This setup is
available only if the equipment has a utility saver input (refer to outdoor equipment
Installation Instructions). This setup controls the response of the equipment when
the utility saver input is active.
DISABLED
means that the curtailment function is
not active.
TURN OFF
means the outdoor unit is to be turned off when the
curtailment function is active.
LOW STAGE
means the outdoor unit will run in
lows stage when the curtailment function is active. After the selections are made,
touch
SAVE
.
A12193
S
Cooling:
Disabled, Low Stage or Turn off
d
Default = Disabled
S
Heat Pump:
Disabled, Low Stage or Turn off
d
Default = Disabled
6.3.10.
Hydronic Airflow
This option allows the installer to select the airflow for the fan coil when paired
with a hydronic coil. After the selections are made, touch
SAVE
.