47
6.3.4.8. Brownout Disable
This option turns off the high voltage brownout detection function in the
outdoor unit control. After the selection is made, touch SAVE.
•
Brownout Disable
: On or Off. Default = Off
6.3.4.9. Low Air Multiplier
Adjusts the airflow speed on non-communicating two-stage units.
Choose 0.65 for units with a Bristol compressor, choose 0.80 (default) for
units with a Copeland scroll compressor.
6.3.4.10. Energy Efficiency
This option is used to input the published ratings of the installed air
conditioner or heat pump as part of the energy tracking calculation. After
the ratings are entered, touch
SAVE
.
6.3.5. Heat Source Lockout
First touch
SETUP
, then touch
HEAT SOURCE LOCKOUTS
to set up
the parameters for the AC/Heat Pump unit.
For hydronic heat applications, this option allows the installer to set the
lockout temperatures below which only the hydronic coil will operate,
and the lockout temperature above which the hydronic coil will not
operate. After the selections are made, touch
SAVE
.