13
• Close to or in direct airflow from supply registers.
• In areas with poor air circulation, such as behind a door or in an
alcove.
4.3.2. Wired Remote Room Sensors
A Remote Room Sensor can be used with the Evolution Connex Control
to take the place of the control’s internal temperature sensor. This allows
the Evolution Connex Control to be mounted in areas with less than
optimal airflow (such as near an exterior door, window or in a closet).
The remote sensor can be wired to the terminal block connectors labeled
S1 and S2 at the control’s backplate, or the ZS1 and ZS1C connection at
the Damper Control Module. In either case, the Evolution Connex
Control will automatically detect the Remote Room Sensor and ignore its
internal temperature sensor.
NOTE:
Humidity sensing will occur ONLY at the Evolution Connex
Control. The wired Remote Room Sensor does NOT have humidity
sensing capability.
4.3.2.1. Wired Remote Room Sensor Averaging
Typically, one wired remote sensor is used but, multiple wired sensors
may be used and averaged in some applications. Averaging requires a
special series-parallel wiring method with a specific number of sensors.
See figure below. It is also important to note the humidity sensor cannot
be remotely located, so do not locate the Evolution Control in an area
where humidity sensing may not be accurate.