43
CONFIGURATION POINTS (CON’T)
BACview Menu
POINT NAME
BACnet Object
RANGE
DEFAULT
ENTRY
HOME>CONFIG>
UNIT>INPUT
INPUT CONFIGURATION
Input 1 Function
ai1_function
1=No Sensor
2=IAO Sensor
3=OAQ Sensor
4=Space RH Sensor
No Sensor
Input 2 Function
ai2_function
1=No Sensor
2=IAO Sensor
3=OAQ Sensor
4=Space RH Sensor
1 (No FIOP)
2 (FIOP)
Input 3 Function
di3_function
1=No Function
2=Compressor Safety
3=Fan Status
4=Filter Status
5=Remote Occupancy
6=Door Contact
Compressor Safety
Input 3 Switch Configuration
di3_type
N/O
N/C
N/O
Input 5 Function
di5_function
1=No Function
2=Fire Shutdown
3=Fan Status
4=Filter Status
5=Remote Occupancy
6=Door Contact
Fire Shutdown
Input 5 Switch Configuration
di5_type
N/O
N/C
N/C
Input 8 Function
di8_function
1=No Function
2=Enthalpy Switch
3=Fan Status
4=Filter Status
5=Remote Occupancy
6=Door Contact
1 (No FIOP)
2 (FIOP)
Input 8 Switch Configuration
di8_type
N/O
N/C
N/O
Input 9 Function
di9_function
1=No Function
2=Humidistat
3=Fan Status
4=Filter Status
5=Remote Occupancy
6=Door Contact
Humidistat
Input 9 Switch Configuration
di9_type
N/O
N/C
N/O
Space sensor type
spt_type
1=T55
2=T56 (use for T59)
3=SPT Sensor
4=None
T55
T5x Override Duration
ovr_dur
0- 24 hours
1
HOME>CONFIG>
UNIT>CALIBRATE
SENSOR CALIBRATION
Space Temperature
lcl_space_temp
Space Temp Calibration
spt_offset
- 9.9- 10° F
0
Space RH
lcl_space_rh
0- 100%
Space AQ
lcl_space_aq
0- 5000ppm
Supply Air Temperature
lcl_sa_temp
- 56- 245° F
Supply Air Temp Calibration
sat_offset
- 9.9- 10° F
0
Outdoor Air Temperature
lc_oa_temp
- 56- 245° F
Outdoor Air Temp Calibration
oat_offset
- 9.9- 10° F
0
TS
-
5580
-
01