30
APPENDIX A - USER INTERFACE MENUS (CON’T)
Status Menu
BACview Menu
POINT NAME
BACnet Object
RANGE
DEFAULT
Field Assistant Menu
STATUS
HOME>STATUS
Equipment Status
mode_status
1=Disabled
2=Test
3=Run
Properties>Equipment>
Status
System Mode
run_status
1=Off
2=Fan Only
3=Economizer
4=Cooling
5=Heating
6=Dehumidification
7=Test
8=Shutdown
9=Unocc Free Cooling (NTFC)
10=Fire Shutdown
11=IAQ Override
12=Pre- occ Purge
Supply Fan Status
sfan_status
Off/Running
Fan Speed
fan_run
1=Off
2=Low
3=Med
4=High
5=On
Supply Fan VFD
vfd_output
0- 100%
Space Temperature - Prime Variable
space_temp
xxx ° F
Supply Air Temperature
sa_temp
xxx ° F
Outdoor Air Temperature
oa_temp
xxx ° F
Space Relative Humidity
space_rh
0- 100 %
Indoor Air CO2
iaq
0- 5000 ppm
Outdoor Air CO2
oaq
0- 5000 ppm
Economizer Output
econ_output
0- 100 %open
Shutdown
shutdown
Inactive/Active
TS
-
5580
-
01