APPENDIX A - USER INTERFACE MENUS (CON’T)
Configuration Menus
BACview Menu
POINT NAME
BACnet Object
RANGE
DEFAULT
Field Assistant Menu
UNIT CONFIGURATION
HOME>CONFIG>
UNIT
UNIT CONFIGURATION
Properties>Equipment>
Configuration>
Unit Configuration
Fan Mode
fan_mode
1=Auto
2=Continuous
3=Always On
Continuous
Power Fail Restart Delay
start_delay
0- 30 sec
5
Fan Off Delay
fan_delay_off
0- 180 sec
90
Minimum Cooling SAT
sat_cl_min
45- 75 ° F
50
Maximum Heating SAT
sat_ht_max
85- 150° F
120
Vent Dmpr Pos / DCV Min Pos
econ_min
0- 100 %Open
20
Economizer Purge Min Pos
econ_purge_min
0- 100 %Open
40
Low Fan Econ Min Pos
econ_min_2
0- 100 %Open
33
DCV Max Vent Damper Pos
iaq_dpr_max
0- 75 %Open
50
Supply Fan Service Alarm Timer
sfan_service_hrs
0- 9999 hr
600
Comp 1 Service Alarm Timer
comp1_service_hrs
0- 9999 hr
0
Comp 2 Service Alarm Timer
comp2_service_hrs
0- 9999 hr
0
Filter Service Alarm Timer
filter_service_hrs
0- 9999 hr
600
Pushbutton Override
pb_enable
Disable/Enable
Enable
Setpoint Adjustment
stpt_adj_enable
Disable/Enable
Enable
Setpoint Adjustment Range
stpt_adj_range
+/- 0- 5 ° F
5
Cooling Lockout Temperature
oat_cl_lockout
0- 80° F
45
Economizer High OAT Lockout Temp
oat_ec_lockout
55- 80° F
75
HP Rev Cycle Lockout Temp
hp_rev_cycle_lockout
- 20- 30° F
- 3
Heating Lockout Temperature
oat_ht_lockout
35- 150° F
65
Pre Occupancy Purge
preocc_purge
Disable/Enable
Disable
Purge Time
purge_time
60 min
0- 240 min
Unocc Free Cool
ntfc_ena
Disable/Enable
Disable
Min Setpoint Separation
min_stpt_sep
2- 10 ° F
5
Occupancy Source
occ_source
1=Always occupied
2=BACnet Schedule
3=BAS On/Off
4=Remote Occ Input
Always Occupied