36
APPENDIX A - USER INTERFACE MENUS (CON’T)
Maintenance Menu
BACview Menu
POINT NAME
BACnet Object
RANGE
DEFAULT
Field Assistant Menu
MAINTENANCE
HOME>MAINT
UNIT MAINTENANCE
Properties>Equipment>
Maintenance
Occupancy Status
occ_status
Occupied/Unoccupied
Temp Compensated Start
- Or-
Learning Adaptive Start
tcs_status
- Or-
aos_status
Inactive/Active
Pre Occupancy Purge
purge
Inactive/Active
Space Temp Sensor
spt_status
1=Sensor Failure
2=SPT Sensor
3=T55/T56
4=Network
6=Locked Value
Setpoint Adjustment
stpt_adj
x ° F
Relative Humidity Source
rh_source
1=N/A
2=Local
3=Network
5=Locked Value
IAQ Source
iaq_source
1=N/A
2=Local
3=Network
5=Locked Value
OAQ Source
oaq_source
1=N/A
2=Local
3=Network
5=Locked Value
Outdoor Air Temperature Source
oat_status
1=N/A
2=Local
3=Network
5=Locked Value
Safety Chain Feedback
safety_status
Off/Run Enabled
Fire Shutdown Status
firedown_status
Run Enabled/Shutdown
Compressor Safety Status
comp_status
Normal/Trouble
Calculated Min Econ Pos
cal_min_econ_pos
0- 100%
Calculated Min PE Pos
cal_pe_stpt
0- 100%
Active Compressor Stages
comp_run
0- 2
Active Heat Stages
heat_run
0- 2
Enthalpy Status
enthalpy_status
High/Low
Humidistat Input Status
humstat_status
High/Low
Filter Status
filter_status
Clean/Dirty
Door Contact Status
door_contact_status
Off/On
Reset Supply Fan Runtime Alarm
sfan_rntm_clr
Run/Clear
Run
Reset Comp 1 Runtime Alarm
comp1_rntm_clr
Run/Clear
Run
Reset Comp 2 Runtime Alarm
comp2_rntm_clr
Run/Clear
Run
Reset Filter Runtime Alarm
filter_rntm_clr
Off/On
Off
OCCUPANCY MAINTENANCE
BAS On / Off
keypad_ovrde
1=Inactive
2=Occupied
3=Unoccupied
Inactive
Schedules
schedule
Unoccupied/Occupied
Pushbutton Override
pb_status
Off/Active
Occupancy Contact
occ_contact_status
Off/On
Override Time Remaining
ovrde_time
0- 240 min
RUNTIME MAINTENANCE
Supply Fan Runtime
sfan_rntm
xxxxx hr
Compressor 1 Runtime
comp1_rntm
xxxxx hr
Compressor 2 Runtime
comp2_rntm
xxxxx hr
Filter Runtime
filter_rntm
xxxxx hr
TS
-
5580
-
01